6.3.2 Advanced menu
.. Bluetooth
Item of the menu needed to the first coupling between an Android device and the control unit. Refer to the Help of the Android application for the
connection procedure.
.. Electrical brake
Short reverse movement with reduced torque to reduce the inertia of the gate. The operation is performed at each stop of the movement except for
fast movement after the intervention of a safety devices.
.. Functioning of closing photocell PHOTO1 moving from closed position
The closing photocell has the following functioning
Closing: immediate inversion of movement
Opening from an intermediate position: no intervention
Opening from closed position:
.. = 0 The gate doesn't move if PHOTO1 beam is cut
.. = 1 The gate moves while PHOTO1 beam is cut
.. Functioning of opening photocell PHOTO2
The opening photocell has the following functioning
Opening: stops the movement and waits until the beam is freed, then moves in opening.
Closing:
.. = 0 Stops the movement and waits until the beam is freed, then moves in opening
.. = 1 No intervention
.. Photocells test
Enabling this function, before each movement starting from still gate, the control unit performs a functional check of the photocells. The check will not
be performed in case of fast movement after the intervention of a safety devices. Follow paragraph 3.6 for the connections of the photocells.
.. Safety edge type
The control unit can work with two different type of safety edge:
..= 0 Mechanical with normally closed contact
..= 1 Resistive 8k2
.. Operation mode of safety edge
To allow the installation of the safety edges in both the directions of movements, it is possible to choose 2 different functioning:
..= 0 Only in closing with total inversion of movement
..= 1 Both directions of movements, stop and short inversion to free the obstacle
.. Safety edge test
Enabling this function the control unit performs a functional check of the safety edge. This function is used if the edge connected to the control unit has
an electronic self test (exp. radio edge R.CO.O). Connect the test contact of the edge to the power supply of the trasmitter of the photocells
(paragraph 3.6) ad enable the self test with low voltage 0Vdc (for the compatibility follow the instruction of the manual of the safety edge).
.. Pedestrian opening
Pedestrian opening can be performed only starting from closed. The parameter sets the opening like a percentage of the total stroke of the first wing.
.. Auto reclosing time from pedestrian opening
Active when the gate is in the pedestrian opening, the gate automatically closes after .. seconds. In this phase the display shows
with the blinking dash, that during the last 10 seconds will be replaced by the count down.
.. Flashing light output mode
It is possible to choose 2 different functioning for the blinker output:
.. = 0 Fixed blinker output. It will be necessary to connect a self flashing blinker (B.RO LIGHT 230 Vac)
.. = 1 Flashing light blinker output. It will be necessary to connect a fix light blinker (B.RO LIGHT FIX 230 Vac)
.. Pre-flashing time
Pre-flashing before each movement in both directions, .. seconds of pre-flashing
.. Courtesy light settings
The control unit has 4 different functionings for courtesy light:
.. = 0 the light switches off at the end of a movement after .. seconds
.. = 1 the light switches off only with closed gate after .. seconds
.. = 2 lighted on for .. seconds from the beginning of a movement, indipendently of the condition of the gate
(the light could switch off before the end of movement)
.. = 3 open gate light - the light switches off immediately when the gate reaches the closed position
.. = 4 open gate light with proportional blinking:
opening – slow blinking
closing – fast blinking
opened – light on
closed – light off
stopped – 2flash + long wait + 2flash + long wait +...
.. Courtesy light timer
Courtesy light activation timer
6-1622189
rev.1
22/05/2015
ITA
ENG
FRA
ESP
DEU