7

INSTALLATION

DANGER!
Danger – high pressure.
▶ Turn off the pressure and vent the lines before loosening
lines or valves.
Risk of electric shock.
▶ Before reaching into the device or the equipment, switch off
the power supply and lock to prevent reactivation.
▶ Observe applicable accident prevention and safety regula-
tions for electrical equipment.
WARNING!
Risk of injury from incorrect installation.
▶ Installation may only be performed by authorized technicians
with the appropriate tools.
Risk of injury from unintentional activation of the system and
uncontrolled restart.
▶ Secure system against unintentional activation.
▶ Following installation, ensure a controlled restart.
CAUTION!
Risk of injury due heavy devices!
▶ During transport or during assembly, a heavy device may fall
and cause injury.
▶ Do not transport, install or remove heavy devices without the
aid of a second person and using suitable auxiliary equipment.
▶ Use appropriate tools.
10
english
Type 2030, 2031, 2031 K, 2032,
Installation
7.1
Before installation
• Before connecting the valve, ensure that the pipelines are
aligned.
• The flow direction is optional.
7.1.1
Installation position general
Installation for self-drainage of the body
It is the responsibility of the installer and operator to
ensure self-drainage.
Installation for leakage detection
One of the bores in diaphragm socket for monitoring
leakage must be at the lowest point.
7.1.2 Installation position 2/2-way valve
Installation position: any position, preferably with the actuator
face up.
To ensure self-drainage:
→ Install body at an angle α = 10° to 55° to the horizontal
(see "Fig. 2").
→ Observe an inclination angle of 1° – 5°.
→ Forged bodies, tube valve bodies and cast bodies feature
a mark which must face upwards ( (12 o'clock position, see
"Fig. 2").
→ One of the bores in the diaphragm socket for monitoring
leakage, must be at the lowest point.
2033, 2037