Dialogic Vision TIGI2U Yükleme - Sayfa 7
Sunucu Dialogic Vision TIGI2U için çevrimiçi göz atın veya pdf Yükleme indirin. Dialogic Vision TIGI2U 15 sayfaları.
The following table summarizes the steps required for installing the Vision Server
TIGI2U:
Step
1
2
3
4
5
6
After the installation is complete, configure the Vision Server TIGI2U as described in
the documentation. Refer to the Accessing Vision Documentation document for
information about accessing the documentation.
Grounding the server
Before connecting the server to a power source, be sure it is properly grounded. The
server must be grounded using a two-hole #10x5/8 ground lug (Burndy
YAV102TC10-90 or equivalent). Use four #10-32 nuts, one under and one on top of
the ground lug as shown:
Tighten each nut to 10 in-lbs torque.
Note: The ground lug and nuts are not included with the server.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Action
Install the Vision Server TIGI2U.
Make a good low impedance connection to earth ground. This is
required because DS-1 connections can be susceptible to
lightning strike or power cross before a power source is provided
for the device.
Provide a power source for the server.
Connect Ethernet interfaces to the device, if applicable.
Ensure that T1 connections are behind a channel service unit
(CSU).
Connect device trunk interfaces, if applicable.
Installing the Dialogic® Vision™ Server TIGI2U
Refer to...
Intel Server Deployment
Toolkit CD
Grounding the server on
page 7
Connecting to a power
source on page 8
Connecting Ethernet
cables on page 8
Connecting to a T1
network on page 9
Connecting T1/E1 trunk
and SS7 signaling cables
on page 9
7