Aquatech Pressmain MG-LT Talimatlar Kılavuzu - Sayfa 4

Kontrol Ünitesi Aquatech Pressmain MG-LT için çevrimiçi göz atın veya pdf Talimatlar Kılavuzu indirin. Aquatech Pressmain MG-LT 20 sayfaları. Tankmatic tank level/temperature monitoring/control unit with smart relay control

Aquatech Pressmain MG-LT Talimatlar Kılavuzu
0.1.7
The equipment must not be pressurised beyond the maximum working pressure as stated on 
pressure sensors/temperature sensors/pumps/pipework/vessels/control panel otherwise serious 
mechanical damage/destruction could occur causing injury to people or property. 
0.1.8
The equipment must not be heated/chilled beyond the maximum/minimum working temperature 
as stated on pressure sensors/temperature sensors/pumps/pipework/vessels/control panel 
otherwise serious mechanical damage/destruction could occur causing injury to people or property. 
0.1.9
Any damage to equipment, sensors, pumpset, vessels, pipework or system components caused by 
misapplication, mishandling or misuse could lead to Electric shock hazard, Burns hazard, Fire hazard, 
Flooding hazard or cause injury to people or property. 
0.1.10
This equipment may contain moving/rotating parts that must remain guarded. Removal of or 
missing guards could lead to serious personal injury. 
0.1.11
Pressure vessels must never be disassembled whilst in use, they contain high pressure air/gas charge 
which could cause injury to people or property.  
0.1.12
Pump motors with lifting eyes; the lifting eyes are only suitable for lifting motors NOT the entire 
pump assembly. This could cause injury to people or property. 
0.1.13
Ensure the base/foundation/plinth/wall to which the equipment is to be attached is sufficiently 
strong enough to carry the entire mass of the equipment including the water that it will contain 
under worst‐case fault conditions. E.g. fully saturated pressure vessel with no air charge, break tank 
full to overflowing, etc. Failure to observe this could cause serious mechanical damage/destruction 
resulting in injury to people or property. 
0.1.14
This equipment contains a fluid which may under certain circumstances leak/drip/spray fluid (e.g. 
servicing, repair or malfunction). Ensure any fluid discharge will not cause damage to the 
surroundings by taking appropriate action. E.g. install in a place that will not be damaged by leakage 
or install in a bunded area with adequate drainage. 
 
0.2  
CAUTIONS FOR INSTALLATION 
0.2.1
READ GENERAL SAFETY INFORMATION 0.0, WARNINGS 0.1 and CAUTIONS 0.2, 0.3 & 0.4 
0.2.2
The unit should only be installed/operated by a competent person; A competent person is someone 
who is technically competent and familiar with safety practices and the hazards involved. 
0.2.3
Do not lift the pumpset (where supplied) by pipework. Lift the pumpset by the container pallet using a 
pallet/forklift or crane by passing strops underneath the skid using a spreader bar. Failure to utilise 
these facilities will result in damage to the pumpset. 
0.2.4
Store in a dry place to avoid damp conditions deteriorating the equipment. 
0.2.5
Protect against dirt, damage and frost. It is absolutely essential that no foreign matter such as pipe 
thread swarf, welding slag, grit or stones are allowed to enter the equipment. Debris of this type can 
cause severe damage to the sensors, mechanical seals, diaphragms and impeller. Frost/freezing will 
damage sensors, pumps/pipework and control panel components. 
0.2.6
The equipment is only suitable for installation in a clean, dust free indoor environment, with adequate 
protection from heat and frost, and sufficient ventilation to ensure cooling of the motors (where 
applicable). Ambient air temperature should be between 5 and 40 degrees centigrade, non‐
condensating. Operation outside of these conditions could seriously damage the equipment. 
0.2.7
If the equipment were to be stored or taken out of service for a period of time (e.g. 1 week or more), 
then we would recommend draining the equipment of all water/liquid (with due regard to any local 
regulations) to prevent frost damage to components. When restarting is required we would 
recommend commissioning by our authorised service agent. 
0.2.8
Ensure the base/foundation/plinth/wall to which the equipment is to be attached has sufficient mass 
compared to the equipment, in order to avoid noise/vibration transmission. E.g. the mass of the base 
should be at least five times the mass of the equipment. 
Aquatech‐Pressmain Instruction manual\Tankmatic smart relay MG‐LT 
Tankmatic Smart Relay 
 
4