Aquatek ATAIOIF Series Kullanım ve Bakım Kılavuzu - Sayfa 15
Su Filtrasyon Sistemleri Aquatek ATAIOIF Series için çevrimiçi göz atın veya pdf Kullanım ve Bakım Kılavuzu indirin. Aquatek ATAIOIF Series 16 sayfaları. Chemical free iron & sulfer filter
Problem
Err - 1001 = Control
unable to sense motor
movement
Err - 1002 = Control
valve motor ran too
short and was unable
to find the next cycle
position and stalled
Err - 1003 = Control
valve motor ran too
long and was unable
to find the next cycle
position
Err - 1004 = Control
valve motor ran too
long and timed out
trying to reach home
position
Possible Cause
Motor not inserted full to engage pin-
ion, motor wires broken or disconnect-
ed
Circuit Board not properly snapped
into drive bracket
Missing reduction gears
Foreign material is lodged in control
valve
Mechanical binding
Main Drive Gear too tight
Improper voltage being delivered to
Circuit Board
Motor failure during a regeneration
Foreign matter built up on Piston and
Seal and Spacer Stack Assemblies cre-
ating friction and drag enough to time
out Motor
Drive Bracket not snapped in properly
and out enough that reduction gears
and drive gear do not interface
Drive Bracket not snapped in properly
and out enough that reduction gears
and drive gear do not interface
UNITED WATER INC.
A
AtAIOIF-S
quAtek
Solution
Disconnect power, make sure motor is
fully engaged, check for broken wires,
make sure two pin connector on motor
is connected to the two pin connection
on the Circuit Board labeled MOTOR.
Press NEXT and REGEN buttons at the
same time for 3 seconds to resynchro-
nize software with piston.
Properly snap Circuit Board into drive
bracket and then Press NEXT and
REGEN buttons at the same time for 3
seconds to resynchronize software with
piston.
Replace missing gears
Open up Control Valve and pull out
piston assembly and Seal and Spacer
Stack Assembly for inspection. Press
NEXT and REGEN buttons at the same
time for 3 seconds to resynchronize
software with piston.
Check Piston and Seal and Spac-
er Stack Assembly, check Reduction
Gears, check Drive Bracket and Main
Drive Gear Interface. Press NEXT and
REGEN buttons at the same time for 3
seconds to resynchronize software with
piston.
Loosen Main Drive Gear. Press NEXT and
REGEN buttons at the same time for 3
seconds to resynchronize software with
piston.
Verify that proper voltage is being sup-
plied. Press NEXT and REGEN buttons at
the same time for 3 seconds to resyn-
chronize software with piston.
Check motor connections then Press
NEXT and REGEN buttons at the same
time for 3 seconds to resynchronize
software with piston.
Replace Piston and Seal and Spac-
er Stack Assemblies. Press NEXT and
REGEN buttons at the same time for 3
seconds to resynchronize software with
piston.
Snap Drive Bracket in properly then
Press NEXT and REGEN buttons at the
same time for 3 seconds to resynchro-
nize software with piston
Snap Drive Bracket in properly then
Press NEXT and REGEN buttons at the
same time for 3 seconds to resynchro-
nize software with piston.
u
G
erIeS
Ser
uIde
15