Panasonic U-20ME1E81 Kurulum Talimatları Kılavuzu - Sayfa 7

Dijital Kamera Panasonic U-20ME1E81 için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. Panasonic U-20ME1E81 25 sayfaları. Wall mounted (k1 type), mini vrf (le1 type), 2way vrf (me1 type), 3way vrf (me2 type)
Ayrıca Panasonic U-20ME1E81 için: Hızlı Referans Kılavuzu (24 sayfalar), Kullanım Talimatları Kılavuzu (26 sayfalar), Kullanım Talimatları Kılavuzu (25 sayfalar), Kurulum Kılavuzu (9 sayfalar), Kurulum Talimatları Kılavuzu (28 sayfalar), Kullanım Talimatları Kılavuzu (10 sayfalar)

Panasonic U-20ME1E81 Kurulum Talimatları Kılavuzu

3. HOW TO INSTALL THE INDOOR UNIT

■ Low Silhouette Ducted Type (F2 Type)

3-1. Required Minimum Space for Installation and
Service
● This air conditioner is usually installed above the ceiling so
that the indoor unit and ducts are not visible. Only the air
intake and air outlet ports are visible from the unit bottom.
● The minimum space for installation and service is shown in
Fig. 3-1 and Table 3-1.
Table 3-1
Type
22, 28, 36, 45, 56
A (Length)
867
● It is recommended that space be provided (450 × 450 mm)
for checking and servicing the electrical system.
● The detailed dimensions of the indoor unit is shown in Fig.
3-2 and Table 3-2.
Table 3-2
Type
A
22, 28, 36, 45, 56
867
60, 73, 90
1,067
106, 140, 160
1,467
g
172
e
h
Unit: mm
60, 73, 90
106, 140, 160
1,067
1,467
B
C
800
450 (Pitch 150 × 3)
1,000
750 (Pitch 150 × 5)
1,400
1,050 (Pitch 150 × 7)
Air intake port side
j
A (Suspension bolt pitch)
B
33.4
D
C
E (Flange O.D.)
54
Air outlet duct side
A (Suspension bolt pitch)
Indoor unit
min.250
Unit: mm
D
E
F
71
592
12
21
792
16
71
1,192
20
a) Refrigerant tubing joint (liquid tube)
b) Refrigerant tubing joint (gas tube)
c) Upper drain port VP25 (O.D. 32 mm)
200 flexible hose supplied
d) Bottom drain port VP25 (O.D. 32 mm)
e) Suspension lug (4 – 12 × 30 mm)
f ) Power supply outlet
g) Fresh air intake port (ø150 mm)
h) Flange for flexible air outlet duct
i ) Electrical component box
j ) Filter
Inspection
access
450 × 450
(Field supply)
(150)
D
a
154
33.4
7
Unit: mm
Electrical
component box
Inspection
access
450 × 450
Refrigerant
tubing
Min.650
Fig. 3-1
290
f
255
i
c
d
26.1
70
90
b
23
140
23
Unit: mm
Fig. 3-2