Alpha Communications TekTone CM800 Kurulum ve Kullanım Talimatları Kılavuzu - Sayfa 5

Kontrol Sistemleri Alpha Communications TekTone CM800 için çevrimiçi göz atın veya pdf Kurulum ve Kullanım Talimatları Kılavuzu indirin. Alpha Communications TekTone CM800 8 sayfaları. Emergency call signaling system

Figure 6—Emergency Call Hook-Up Diagram with SF117/4 series Continuous Duty Door Release,
LI381 Corridor Light, LI123B Corridor Light with Buzzer, and BE005 Corridor Bell
TO ADDITIONAL
EMERGENCY
SWITCHES
SF117/4(B,C)
EMERGENCY
SWITCH
Notes:
1. Use 24 VAC connections on SS106 transformer. To calculate
current requirements, add currents of all devices on at the
same time. Current requirements are as follows:
Corridor Lamp with buzzer– .16 amps
Corridor Bell– .2 amps
Door release– .3 amps
Annunciator lamp– .04 amps
2. Wiring must be #18 gauge except where shown otherwise.
3. BE005 connects to emergency switch on the same floor only.
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
RECTIFIER
-
(See NOTE 9)
+
LI123B
LAMP
w/ BUZZER
DOOR RELEASE
SF117/4(B,C)
EMERGENCY
SWITCH
#22
FACTORY CONNECTED
RECTIFIER
-
(See NOTE 9)
+
BE005
CORRIDOR
BELL
LI381
DOME
LAMP
DOOR RELEASE
ANNUNCIATOR LAMPS
TEST BUTTON
NOTE: PM110/4N MODULES ONLY
4. Door release (if used) must be 24 VDC continuous duty type.
5. Switch current capacity is 3 amps.
6. Power supply maximum current is 1 amp.
7. See Figure 4 for additional wiring details.
8. Switches shown in the OFF position.
9. Rectifier RUFO® Model 1005 is not available from TekTone®.
IL514 CM800/CM900 Emergency Call System Manual • Page 5
TONE
SPEAKER
SS106
24 VAC
TRANSFORMER
(See NOTE 1)
PK2019/A
117 VAC
R1
R2
TONE
R3
OFF
LAMP
B
TONE
OFF
BUTTON
A
W
S
P
D
N
T1
T2
SS106
16 VAC
TRANSFORMER
117 VAC
IL514 General Wiring Figure 5 Rev2 110210 1