Chapter 3—Programming & Operation
Receiver Menus
There are three main menus (see Figure 5):
• Install & Service
• Event Log
• Point Stataus
Select the Install & Service menu to program relay outputs,
change the password, view the signal strength, delete points,
register transmitters or set up points for any of the programmed
transmitters. Note: A password is required to access the Install
& Service menu. The default password is 3446.
Program Relay Outputs
1. From the Install & Service menu, press the
the PROGRAM OUTPUT prompt.
2. PROGRAM OUT 01 is displayed.
3. Using the
and
buttons to scroll, select OUTPUT 01
UP
DOWN
for programming, and press the
4. OUT 01 FOLLOWER is displayed. Use the
buttons to select one of the following four options, and then
press the
button to select the appropriate output type:
ENTER
Follower—The relay output reflects the transmitter's alarm
status. Press the
ENTER
Latching—The relay output turns on when activated and
remains on until the receiver is reset. Press the
button to select this option.
Figure 4—NC505ES Indicators & Function Buttons
K
Page 4 • IL882 NC050ES Remote LCD Receiver Manual
button at
ENTER
button.
ENTER
and
UP
DOWN
button to select this option.
ENTER
Inovonics
A
READY
B
E
C
D
F
Toggle—The relay output changes state each time the device
sends a new activation. A minimum of five seconds must
elapse before the relay output can send a new activation.
•
Press the
ENTER
display shows INACTIVE. Inactive time prevents
output chatter. The default is 4.0 seconds. The valid
range is 2.0 to 99.5 seconds, in half-second increments.
•
Use the
and
UP
digits; press the
to the next digit.
•
When finished, press the
complete the setting.
Momentary—The relay output turns on for a programmed
number of seconds, then turns off, regardless of the
device status.
•
MOMENT displays when selected. This sets the
number of seconds that the output will remain acti-
vated. The default is 4.0 seconds. The valid range is
0.5 to 99.5 seconds, in half-second increments.
•
Use the
and
UP
digits; press the
to the next digit.
•
When finished, press the
complete the setting.
5. The display shows PGM DONE. Press the
program another relay output, or press the
return to the Install & Service menu.
6. Repeat steps 1–5 for relay outputs 02–06.
G
H
I
J
Copyright © TekTone Sound & Signal Mfg., Inc. All Rights Reserved.
button to select this option. The
buttons to scroll through the
DOWN
button to select and advance
ENTER
button again to
ENTER
buttons to scroll through the
DOWN
button to select and advance
ENTER
button again to
ENTER
button to
ENTER
button to
BACK
A - OUTPUT LED
B - FAULT LED
C - NOT USED
D - POWER LED
E - LCD DISPLAY
F - DECODE LED
G - UP BUTTON
H - DOWN BUTTON
I - BACK BUTTON
J - ENTER BUTTON
K - RESET BUTTON