5c) Configuration of the
DIP Switches
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20200513
5. Electrical Connection and Configuration of the
Hold-Open System with RZ-24-05 - cont.
DIP switch 1
When DIP switch 1 is set to OFF (factory setting), a tripping is stored.
This means that a manual push button release is not automatically reset
and the reset button must be operated manually.
DIP switch 1 in position ON realizes the automatic reset mode. This
means that a tripping is automatically reset after 3 s when the detection
loop is ready.
DIP switch 2
The DIP switch 2 in position OFF (factory setting) realizes the central
closing via the external input. For this purpose, 24 V are briefly applied
to the input. Central closing can be used to close doors (only with
electromagnets) without triggering the detection loop of the RZ-24-05.
This function is not a closing in case of fire, but only realizes the closing
of the fire and smoke protection closures, e.g. at the end of the working
day. The electromagnet output is switched off for approx. 3 s when the
24 V are applied to the external input.
The DIP switch 2 in position ON enables an external reset of the central
via the external input 12 or 14.
Control unit rear side
Technical Manual
RZ-24-05 Central
DIP switches
for the
operating
modes
Ill. 3
Page 07.021.09