AXITEC AC-350M/72V Kurulum Kılavuzu - Sayfa 3

İnvertör AXITEC AC-350M/72V için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. AXITEC AC-350M/72V 17 sayfaları.

1. General Safety Precautions

1.1.
Photovoltaic modules have no on/off switch. Modules can be rendered inoperative only by
removing them from sunlight, or by fully covering their front surface with cloth, cardboard,
or other completely opaque material, or by working with modules face down on a smooth,
flat surface.
1.2.
Photovoltaic modules produce DC electricity when exposed to light and therefore can
produce electrical shock or burns. Modules produce voltage even when not connected to
an electrical circuit or load. Modules produce nearly full voltage when exposed to as little
as 5% of full sunlight both current and power increase with light intensity. Use insulated
tools and rubber gloves when working with modules in sunlight. It would be best by
covering their front surface fully with completely opaque materials when operating on the
modules. Artificially concentrated sunlight shall not be directed on the module.
1.3.
Modules may produce higher output than the rated specifications. Industry standard
ratings are made at conditions of 1000 watts/m
Reflection from snow or water can increase sunlight and therefore boost current and
power. In addition, temperature below 25℃ can substantially increase voltage and power.
1.4.
Axitec LLC modules are constructed with tempered glass, but still must be handled with
care, If the front glass is broken or if the polymer back-skin is torn, contact with any module
surface or the frame can produce electrical shock, particularly when the module is wet.
Broken or damaged modules must be disposed of properly.
1.5.
Axitec LLC modules are intended for use in terrestrial applications only, thus excluding
aerospace or maritime conditions or use with sunlight concentration. Excluded applications
include, but are not limited to, installations where modules are likely to come in contact
with any salt water or where likely to become partially or wholly submerged in fresh or salt
water, we suggested that the modules should installed at least 500m away from the sea.

2. Codes and Regulations

The mechanical and electrical installation of Module systems should be performed in accordance with all
applicable codes, including electrical codes, building codes, and electric utility interconnection
requirements. Such requirements may vary for mounting location, such as building rooftop or motor
vehicle applications.
Requirements may also vary with system voltage, and for DC or AC application. Contact local authorities
for governing regulations.

3. Mechanical Installation

The module is considered to be in compliance with UL 1703 only when the module is mounted in the
manner specified by the mounting instructions below. Any module without a frame (laminate) shall not
be considered to comply with the requirements of UL 1703 unless the module is mounted with
Installation Manual
2
and 25℃ cell temperature, AM 1.5.
Page 2 / 16