ABB ACS550-U1-08A8-4 Hızlı Başlangıç Kılavuzu - Sayfa 2
Kontrolör ABB ACS550-U1-08A8-4 için çevrimiçi göz atın veya pdf Hızlı Başlangıç Kılavuzu indirin. ABB ACS550-U1-08A8-4 2 sayfaları. Drive low voltage ac drives acs550 series
9. Install the cable clamp(s)
for the control cable(s).
(Power/motor cables and
clamps not shown in the
figure.)
Wiring the controls
1. Strip control cable sheathing
and twist the copper screen into a
pig-tail.
2. Route control cable(s) through
clamp(s) and tighten clamp(s).
3. Connect the ground screen pig-tail
for digital and analog I/O cables at
X1-1. (Ground only at the drive end.)
4. Connect the ground screen pig-tail
for RS485 cables at X1-28 or X1-32.
(Ground only at the drive end).
5. Strip and connect the individual
control wires to the drive terminals.
See Control connections below
or, for more information, see User's
Manual.
Warning! The maximum voltage for digital inputs
is 30 V.
6. Install the conduit/gland box cover (1 screw).
ABB Standard Macro
Check installation
Before applying power, perform the following checks.
Reinstall the cover
1. Align the cover and
slide it on.
2. Tighten the captive
screw.
3. Install the control
panel.
Apply power
Always reinstall the front cover before turning
power on.
Warning! The ACS550 will start up automatically at
power up, if the external run command is on.
1. Apply input power.
When power is applied to the ACS550, the green LED comes
on.
Note!
Before increasing motor speed, check that the
motor is running in the desired direction.
Start-up
I
n start-up, enter motor data (collected earlier)
and, if needed, edit parameters that define how
the drive operates and communicates.
Assistant Control Panel
The Start-up Assistant steps through typical start-up selec-
tions, and runs automatically upon the initial power up. At
other times, use the steps below to
run the Start-up Assistant.
1. Use the MENU key to access the
Main menu.
2. Select ASSISTANTS.
3. Select Start-up Assistant.
4. Follow the screen instructions to
configure the system.
Note!
For common parameters and menu items,
use the Help key
to display descriptions.
If you encounter alarms or faults, use the Help key
or refer to chapter Diagnostics in User's Manual.
Basic Control Panel
The Basic Control Panel does not include the Start-up Assis-
tant. Refer to section "How to start up the drive" in the User's
Manual and manually enter any parameter changes desired.