Arc-Zone AZP-BT-003182-110V Kullanım Kılavuzu - Sayfa 8

Su Sebili Arc-Zone AZP-BT-003182-110V için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Arc-Zone AZP-BT-003182-110V 8 sayfaları. Water cooling system

Troubleshooting Unit

Issue
Power switch doesn't
work
The fuse is fused
The fan doesn't
rotate
Water not flowing
out
Not enough water
flowing out

Wiring Diagram

8
Cause
1�
The switch is broken
2�
AC230V is disconnected
3�
Fuse is in short curcuit
1�
The amperage of the fuse is
too low
2�
The motor of water pump or
fan is in short curcuit
1�
There is a problem with
AC230V power
2�
There is a problem with fan
1�
Gas filled into the water way
system
2�
There is a fault in the water
pump
3�
There is a serious blockage in
water way system
1�
There is slight blockage in
water way system
2�
There is a problem with water
pump
Arc-Zone.com, Inc. • 1331 Specialty Dr. • Vista, CA 92081
Tel. 1.760.931.1500 • Email: [email protected]
Solution
1�
Change switch
2�
Check the incoming line and switch
spot
3�
Change fuse
1�
Exchange the fuse between 3A and
5A
2�
Exchange the motor
1�
Check power supply
2�
Check and repair the fan
1�
Can connect the pipe at the outlet
and suck out air
2�
Check and repair water pump
3�
Check and repair water way
1�
Check and repair water way system
(inlet of the pump)
2�
Check and repair water pump