ABB Jocab Safety Vital 3 Kullanım Talimatı - Sayfa 9
Kontrolör ABB Jocab Safety Vital 3 için çevrimiçi göz atın veya pdf Kullanım Talimatı indirin. ABB Jocab Safety Vital 3 11 sayfaları. Safety controller
Ayrıca ABB Jocab Safety Vital 3 için: Manuel (14 sayfalar)
Technical data
Supply
Nominal voltage
Tolerance
Max interruption
Recommended external fuse
Safety outputs
Solid state:
Output voltage (nominal):
Output voltage by load:
Max. load:
Short circuit protection
Output – 0V
Output – +24 V
Relay output:
Max voltage
Max. load
Non-safe output
Output voltage (nominal):
Max load
General
Enclosure
Response time
Relay output (Q1, Q11)
Solid state safety outputs (Q2, Q12)
Solid state non-failsafe output (Q13)
Ambient air temperature:
Temperature, transportation and storage:
Degree of protection:
Enclosure:
Terminals:
Vital2&3_Manual_v1D
24 VDC
+/-15%
20 ms
6A
Q2, Q12
- 24V
> 22V at 800 mA / 24V supply voltage
23.3 V at 150 mA / 24V supply voltage
800 mA
Yes
Normally (Not guaranteed)
1L - Q1, 11L - Q11
250 VAC
2 A nominal
Q13
+24V
1 A
45 x 84 x 118 mm (w x h x d)
15 – 24 ms
11 – 20 ms
11 – 20 ms
-10°C - + 50°C
- 25 - +50°C, <24h +70°C
IP 40, IEC 60 529
IP 20, IEC 60 529
9