unit to trip. When the unit trips the normally open contacts will close and the normally closed
contacts will open or visa versa depending on which contacts are used. If the CTS 9000
IRRD is tripped and you wish to reset it, insure the rip in the conveyor belt has been fixed or
the object has been removed from the belt. Once the problem, which caused the trip, is
corrected, press the wash button and clear the catch plate of any material. Then reset the
CTS 9000 IRRD by pressing the reset button. The DELAY TIME SELECTOR in the control
box can set the time that the infrared beam must be broken to trip the unit. When the unit is
tripped the lockout led will be illuminated and the trip led will be illuminated every time the
infrared beam is broken.
M
aintenance:
If the covers of t
he CTS 9000 IRRD are dirty and you wish to clean them without tripping the
unit, press the wash button to disable the infra-red beam. The amount of time needed to
clean the lenses or wash down the unit can be set using the SET WASH TIME selector in
the control box. When the unit is in wash mode the wash led will be illuminated and the
covers may be cleaned without tripping the unit. An audible alarm will sound for 30 seconds
before the unit returns to normal working operation..
T
rouble-Shooting:
YES
Is TRIP LED
Illuminated?
Check All
Connections and
Power Source
Establish Reliable
Power Source
M
aintenance Schedule:
1
.
It is recommended that all nuts, bolts, screws and connections be checked and
tightened every six months.
Remove Covers
from Send/
Recieve Units
With Beam
NO
Obstructed, will
Unit TRIP?
YES
Return Unit to
Service
YES
Does Unit Reset?
NO
Are Beams/Boxes
YES
Misaligned
(Inside Boxes)
-Damaged-
NO
NO
Consult
Factory
3
Replace/Clean
Lens Covers
Align/Replace
Boxes
With Beam
Obstructed, will
Unit TRIP?
YES