The CM430S module closest to the panel (Location 1) has to be set to 'TCP Server' and have its 'Remote Host IP Ad-
dress' set to the IP address of the Remote CM430S unit. The table below is an example of configuring both the Client
and Server modules.
Device IP
Subnet Mask
Gateway
Primary DNS
Work Mode
Destination Port
Destination IP/DNS
IP Mode
After all settings have been complete, click 'Apply' and the changes will take effect. Note: It is best to power cycle the
module after any changes.
Connection Diagram - Point to Point Configuration
A pair of CM430S modules is required for each link as shown below. Remote locations will require a local power
supply wih backup battery to maintain connectivity during power outages. A CM720 1 amp or CM723 5 amp power
supply module would be suitable for this task.
Type: Static IP
IP Address: 192168.1.5
Connection Mode: TCP Server
-
-
-
-
+
+
+
+
B A
B A
B A
B A
Module LAN
Module LAN
Module LAN
PANEL LAN
Reset
Reset
Reset
Reset
Page
4
P/N: CM430SIRG Rev 1.2
Option
Table 4: Example Point to Point Configuration
Location 1
Not Used
IN
IN
IN
IN
OUT
OUT
OUT
OUT
Protect
Protect
Protect
Protect
RS232
RS232
RS232
RS232
Not Used
Not Used
Not Used
Not Used
Figure 3: Sample Point to Point Wiring
NOTE: LAN A OUT, LAN B OUT and
the Protect Switch are for Future Use
Location 1
SERVER
192.168.1.5
255.255.255.0
192.168.1.5
168.95.1.1
TCP SERVER
4196
192.168.1.5
Static
Location 2
Reset
Location 2
CLIENT
192.168.1.6
255.255.255.0
192.168.1.5
168.95.1.1

TCP CLIENT

4196
192.168.1.5
Static
Type: Static IP
IP Address: 192168.1.6
Connection Mode: TCP Client
Not Used
B A
Module LAN
IN
OUT
Power Supply
Protect
RS232
Not Used
E&OE