9. UNPACKING

9.1. Inspection

Upon receiving a shipment, of battery cells, it is
advisable to open the shipping containers and carefully
check the cells and hardware against the packing list.
The contents of each consignment are carefully inspected
by FET before shipment. Any damage must be reported
immediately to the carrier and the damaged items
retained for inspection by the carrier's representative.

9.2. Handling

AGM batteries units are shipped fully charged and must
be treated with care at all times. The product is capable
of supplying high short circuit currents, even if the case
or lid is damaged. Always lift the individual unit from
underneath, or by the build-in-lifting handles ( please
also refer to "Battery Installation" section ). Never apply
force to, or drop anything on, the terminal posts: doing
so may damage the threads or the post seals.

10. STORAGE

10.1. Storage prior to installation

VRLA batteries range are delivered activated/filled and
charged ready for installation. If they cannot be installed
immediately, the following instructions need to be
respected.

10.2. Storage Conditions

A good storage practice requires as follows:
 Battery storage area has to be clean, cool and dry.
 Surroundings have to be kept clean.
 Elevated temperatures, direct and indirect sunshine
have to be avoided.
 Optimum storage temperature range is -10°C to
+30°C.
 Avoid storage in ambient with a relative humidity
greater than 90%.
Battery cells must be protected from harsh weather,
moisture and flooding.
 Storage on a pallet wrapped in plastic material is
permitted,
in
recommended in rooms where temperature fluctuates
significantly, or if high relative humidity can cause
condensation under the plastic cover.
 With time, this condensation can cause a whitish
hydration on the poles and lead to high self-discharge
by leakage current.
 Atmospheres with chemical contaminants have to
avoid.
 Do not load other merchandise on top of unprotected
batteries.
 Battery cells must be protected from dropping
objects, from falling down and falling over.
This document and the confidential information it contains shall be distributed, routed or made available solely with written permission of FIAMM Energy Technology.
FIAMM Energy Technology S.p.A. reserves the right to change or revise without notice any information or detail given in this publication.
Installation & Operating Instruction -Technical Manual
principle.
However,
it
 Battery cells must be protected from short-circuits by
metallic parts or conductive contaminations.
 Avoid storing of unpacked battery cells on sharp-
edged supports.
 Stacking of pallets is not permitted unless otherwise
specified.
 It is recommended to realize the same storage
conditions within a batch, pallet or room.

10.3. Storage time / Temperature

VRLA battery ranges have a shelf life of 6 months at a
storage temperature of 20°C.
The temperature has an impact on the self-discharge rate
of battery cells.
Higher temperatures increase the rate of self discharge
and therefore storage life is reduced.
FET AGM batteries have a self discharge rate of ≤ 2%
per month at 20°C and therefore are stored for prolonged
periods of time.
MAXIMUM storage period before refresh at the given
average storage ambient temperature is as follows :

10.4. Storage / Recharge

As during storage batteries will lose part of their capacity
due to self discharge (≤ 2% per month at 20°C), a
refreshing charge must be given :
1. when MAXIMUM STORAGE TIME is reached
2. when the OCV (open circuit voltage)
approaches 2.11 V/cell
Recharge the cells as directed in FET'S instruction table
for AGM battery type. (Usually at 2.4 volt per cell for a
period of 24 hours at 20°C).
is
not
Fig. 8 : Storage time versus temperatures
Edition 03/2018 Rev.7
6 months at 20°C
4 months at 30°C
2 months at 40°C
OR
whichever occurs first.
Recharge is
not necessary
Refreshing charge
must be applied as
soon as possible
It is important
to avoid this
area