FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual
Connection of the battery to the rectifier/load
The end positive terminal of each string of batteries should be connected to the positive terminal of the
charger, and the battery negative to the charger negative. Same procedure needs to be used for load
connections. A proper selection in cables and connectors should be used to avoid excessive voltage
drop, as well as overheating in case of high rate discharge. If a large section of cables are used their
weight should not stress cell/block terminals. A good method to use is to affix cables on the rack or the
nearby wall.

3 CHARGING

Introduction
After installation, in order to ensure the best protection against power failures, it is necessary that
batteries are kept in the following conditions:
• float charged throughout their standby period;
• fully recharged soon after a discharge.
Recharging process can be performed in several ways, depending on the site and equipment
conditions, but there are two main methods:
• float voltage recharge
• boost charge
The IU recharge method, also known as the modified constant voltage recharge, has been used for
many years and in a variety of applications. This method combines the need to have the battery quickly
recharged while ensuring maximum battery life. With this method, recharge starts at a constant current
rate. The voltage increases up to a pre-set value. The pre-set voltage is maintained and the current
then decreases to a minimum defined value. Finally, the recharge is completed at a final constant
voltage value equal to or less than that defined for float charge with the current decreasing to the value
used in float.
For UPS systems that do not utilize a constant float voltage charging profile or use an
Advanced Battery Management charging profile please set the charging parameters per
table 3.
Table 3 – ALTERNATE CHARGING PROFILE SETTINGS
FLX MODEL
12FLX200, 12FLX300, 12FLX350
12FLX400, 12FLX500, 12FLX540
Recommended procedure for initial charging
For a safe installation of FIAMM FLX batteries only constant voltage chargers should be used.
The best charging method operates with a preset constant voltage value supplying an automatically
limited charging current. It is called constant voltage charging with current limit and automatic
crossover.
An initial charge of 2.35 to 2.40 volts per cell for at least 24 hours (at 77° F) is suggested during
commissioning or before a capacity test in order to be sure that the battery is in fully charged condition.
This document and any confidential information it contains shall be distributed, routed or made available solely with written permission of
FIAMM. FIAMM reserves the right to change or revise without notice any information or detail given in this manual
CURRENT LIMIT
25 amps
50 amps
December 2012
VOLTAGE
2.30 v5cell
2.30 v5cell