Cisco 4006 - Catalyst Switch Güç Kılavuzu - Sayfa 2

Anahtar Cisco 4006 - Catalyst Switch için çevrimiçi göz atın veya pdf Güç Kılavuzu indirin. Cisco 4006 - Catalyst Switch 4 sayfaları. User manual

Cisco Catalyst 4006 Switch
Fig 1. 4006 Switch
Powering IP phones from the Catalyst 4006 Switch requires the addition of an external
power shelf (Fig 2) and power modules (Fig 3.). The total power draw for a totally
utilized switch is just above 3000 Watts.
Recommended UPS: SYH6KNRMT-P1
This is a 4.2 KW Symmetra RM UPS with an N+1 Redundant architecture that will
provide ten minutes of runtime at full load. This product requires an L6-30R for input
and ships standard with two L6-20R, one L6-30R, and a step down transformer (SYTF2)
with twelve 5-20 outlets. The transformer plugs directly into the output L6-30R. The
customer should order the 4006 switch with NEMA 5-15P plugs for each power supply.
Fig. 4 SYH6KNRMT-P1
front view
(figure 4, 5, and 6 below)
Fig. 5 SYH6KNRMT-
P1 rear view
Fig 2. External Power Shelf
Fig 3. External Power Supply
Fig. 6 SYTF2 front
and rear