Parameter data record
You specify in the parameter data record for PROFIenergy which I/O modules (slots) are
controlled with the PROFIenergy commands.
The following table shows the content of the parameter data record for PROFIenergy, index
3, which you create yourself and can transfer to the interface module.
Table 2- 3
Byte
0
1
2
3
:
64
65
The specific behavior depends on the used I/O module (with a digital input module, for example,
1
the sensor supply is turned off or the outputs are without power supply and voltage supply with an
analog output module)
An analog output module (e. g. with the output range 0 mA to 20 mA, ± 20 mA) or a digital output
2
module issues the value "0".
Error messages
The following table shows which error messages the feedback data record returns, if
necessary:
Table 2- 4
Error code
80B1
80E0
80E1
Interface module IM 157-1 PN (6ES7157-1AB00-0AB0)
Manual, 12/2016, A5E32347036-AD
Parameter data record for PROFIenergy (version 2), index 3
Element
Version
Number of blocks
Block 1
Slot num-
ber
Mode
:
:
Block 32
Slot num-
ber
Mode
Error messages
Meaning
Impermissible length
H
Error in header information
H
Parameter error
H
at least one I/O module does
not support PROFIenergy
A parameter value has been
incorrectly encoded
Code
Explanation
02
Cannot be modified
D
01
to 34
Slots 1 to 34 depending on the configuration of
D
D
the distributed I/O system ET 200AL
00
Not assigned
D
01
to 34
I/O module slot with PROFIenergy
D
D
0
: PE_MODE_PROCEED, proceed at "Pause"
D
1
: PE_MODE_SHUTDOWN, shut down at "Pause"
D
3
: PE_MODE_LAST_VALUE, last output or measured value is
D
retained
4
: PE_MODE_SUBST_VALUE, substitute value "0"
D
:
See Block 1
Check the length of the data record
Check the data record header information
Check the content of the data record and correct the
parameter assignment error before starting the
"Pause". Parameter assignment errors which are
not corrected can result in incorrect I/O module
shutdown behavior.
Product overview
2.3 Functions
1
2
19