Ayrıca Siemens SIMATIC ET 200SP HA için: Manuel (32 sayfalar), Manuel (50 sayfalar), Manuel (34 sayfalar), Manuel (38 sayfalar), Ekipman Kılavuzu (44 sayfalar), Ekipman Kılavuzu (50 sayfalar), Ekipman Kılavuzu (38 sayfalar), Ekipman Kılavuzu (46 sayfalar), Ekipman Kılavuzu (42 sayfalar), Ekipman Kılavuzu (36 sayfalar), Ekipman Kılavuzu (38 sayfalar)

Siemens SIMATIC ET 200SP HA Ekipman Kılavuzu
Technical specifications
Article number
Digital outputs, parameterizable
Short-circuit protection
Open-circuit detection
Overload protection
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
Load resistance range
Output current
Output delay with resistive load
Parallel switching of two outputs
Switching frequency
Total current of the outputs
Total current of the outputs (per module)
horizontal installation
vertical installation
30
Response threshold, typ.
with resistive load, max.
on lamp load, max.
lower limit
upper limit
for signal "0" residual current, max.
"0" to "1", typ.
"1" to "0", typ.
for uprating
for redundant control of a load
with inductive load, max.
on lamp load, max.
Current per channel, max.
– up to 30 °C, max.
– up to 40 °C, max.
– up to 50 °C, max.
– up to 60 °C, max.
– up to 70 °C, max.
– up to 30 °C, max.
– up to 40 °C, max.
– up to 50 °C, max.
– up to 60 °C, max.
6DL1132-6BH00-0PH1
Yes
Yes; Ensure sufficient low-resistance cable routing
to the sensor/actuator in order to attain the re‐
sponse threshold. Depending on the cable cross-
section used, there may be constraints regarding
the usable length of cable.
0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
Yes; 0.7 mA test current for wire-break diagnostics;
this value is doubled in the case of IO redundancy
Yes
L+ -(37 to 41V)
Yes
0.5 A
5 W
48 Ω
12 kΩ
0.7 mA; Test current for wire-break diagnostics; this
value is doubled in the case of IO redundancy
50 µs
100 µs
No
Yes
2 Hz
10 Hz
0.5 A
8 A
8 A
8 A
5.5 A
3 A
8 A
6.33 A
4.67 A
3 A
Equipment Manual, 10/2021, A5E39265993-AD
DQ 16x24VDC/0.5A