Siemens SIVACON Kurulum Kılavuzu - Sayfa 12

Endüstriyel Ekipmanlar Siemens SIVACON için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. Siemens SIVACON 34 sayfaları. Distribution systems installation and maintenance instructions for power factor correction (pfc) capacitors

Siemens SIVACON Kurulum Kılavuzu
Mounting
3.1 Mounting the capacitors
The PhaseCap Premium, PhaseCap Compact and PhaseCap Energy+ (Height of capacitor
≤ 224 mm) capacitor series may be mounted in the vertical or horizontal position.
Note
The pictures depicted above are for illustration purposes only. Actual sample will be as per MLFB
type.
When mounting in horizontal position, additional mechanical support is recommended to
prevent breaking of the mounting bolt in case of mechanical shock or vibrations. This support
should be placed at short distance below the bead at the top end of the capacitor.
The PhaseCap HD, PhiCap and PhaseCap Energy+ (Height of capacitor > 224 mm) and
DeltaCap capacitors series may be mounted only in the vertical position:
Mounting conditions
PFC capacitors must be installed in a cool and well ventilated place, and not close to objects that
radiate heat such as filter circuit reactors and furnaces, or in the direct sunlight.
12
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A