Overview of NEC Article 409
The "NFPA 70: National Electrical Code" includes "Article 409" on the Construction of
Industrial Control Panels operating at 600 volts or less.
Section 409.2: definition of industrial control panels
Section 409.2 defines an industrial control panel as:
"An assembly of two or more components consisting of one of the following:
1. Power circuit components only, such as motor controllers, overload relays, fused
disconnect switches, and circuit breakers
2. Control circuit components only, such as pushbuttons, pilot lights, selector switches,
timers, switches, control relays
3. A combination of power and control circuit components"
These components are mounted in an enclosure or panel with the associated wiring and
terminals.
The industrial control panel does not include the controlled equipment.
Section 409.110: Marking of the short-circuit current rating
Section 409.110 requires a short-circuit current rating (SCCR) to be marked on all industrial
control panels. This rating must be based on the rating of a listed and labeled assembly or
on another approved method for determining the rating. It also includes a fine print note
(FPN) reference to UL 508A Supplement SB as an example of an approved method for
determining the SCCR that may be marked on the panel.
Short-circuit current rating (SCCR) of industrial control panels
Reference Manual, 06/2013, A5E31896849002A/RS-AA/001
2
9