Flowrite™ 599 Series High Pressure Close-Off Two-Way Valves 2-1/2 to 6-inch
Flanged Iron Bodies ANSI Classes 125 and 250

Installation

Siemens Industry, Inc.
Install the valve so that the flow follows the direction of the arrow indicated on the valve
body identification tag.
CAUTION:
Install the valve assembly with the actuator above the valve body. The
valve and actuator can be installed in any position between:
Horizontal to the valve; and
Vertical above the valve.
It is not recommended to install the valve assembly below horizontal or
upside down.
For flange dimensions and bolt hole information, see 155-303P25 (TB 248).
Allow sufficient space for servicing the valve and actuator. See Table 11 for valve
body dimensions. See Figure 7 and Table 10 for dimensions of the service
envelope recommended around the actuator.
NOTE:
Instructions for field mounting an actuator, spring adjustments, wiring diagrams,
and start-up are covered in the Technical Instructions and Installation Instructions
for each actuator.
Figure 4. Recommended Installation Orientations.