Installation Instructions
Model ZIC-4A
Zone Indicating Card

INTRODUCTION

Features

P/N 315-033050-15
The Model ZIC-4A from Siemens Industry, Inc. is a zone
indicating card that provides notification appliance circuits
for the FireFinder-XLS/Desigo Fire Safety Modular/
Cerberus PRO Modular system. It has 4 outputs that can
be configured for Class A or Class B and control of audible
and visual notification appliances such as horns, speakers,
bells, strobes etc. Its outputs can also be configured as
connection to Municipal Tie, Releasing Service per NFPA
13 and 2001 or as a connection to a Leased Line remote
monitoring circuit.
Each zone can be configured independently for different
usages as programmed in the Zeus tool and can be
controlled automatically by program logic or manually
using the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo
Fire Safety Modular), FCM2041-U3 (Cerberus PRO
Modular). During the initial power-up condition, each
zone on the ZIC-4A is configured as a steady NAC, Class
A configuration with 2A current limit. The ZIC-4A then
sends a message to the PMI/PMI-2/PMI-3 (XLS),
FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3
(Cerberus PRO Modular) indicating that it is
unconfigured.
The ZIC-4A supports synchronized and non-synchronized
strobes. This selection is available in the Zeus tool under
the detail properties for each ZIC-4A circuit. Synchroniza-
tion across multiple ZIC-4A cards is automatic as a part of
the FireFinder-XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular operating characteristics. Refer to docu-
ment P/N 315-096363 for a list of strobes that support
synchronization.
ZIC-4A features are as follows:
Class A / Class B circuit configuration
Zones can be configured independently
Can have independent input source for each output
Zone input voltage supervision
Zone output supervision
Intelligent self-restoring power limiting
Coded signal synchronization capability
Card level Ground Fault detection
Communicate H-Net protocol
Uploadable firmware update
Ability to pass through up to 3A per circuit
RESET
POWER
CARD FAIL
CAN FAIL
HNET FAIL
GND FAULT
ZONE 1 ACTIVE
ZONE 2 ACTIVE
ZONE 3 ACTIVE
ZONE 4 ACTIVE
HNET/CAN
Figure 1
ZIC-4A Zone Indicating Card
Siemens
Siemens
Siemens Industry
Industry, , , , , Inc.
Industry
Siemens
Siemens
Industry
Building
Building
Building
Building T T T T T ec
Building
ec
ec
ec
echnologies Di
hnologies Di
hnologies Di
hnologies Di
hnologies Division
ZIC-4A
TRBL
TRBL
TRBL
TRBL
HUNDREDS
TENS
ONES
Industry
Inc.
Inc.
Inc.
Inc.
vision
vision
vision
vision