Siemens SITRANS L Pointek ULS200 Kullanım Talimatları Kılavuzu - Sayfa 13
Anahtar Siemens SITRANS L Pointek ULS200 için çevrimiçi göz atın veya pdf Kullanım Talimatları Kılavuzu indirin. Siemens SITRANS L Pointek ULS200 47 sayfaları. Ultrasonic non-contacting switch
Operation status - run mode
5.3
Quick start
To set a basic high/low application where you can easily adjust the measured distance, use
the method below. The device relays are preset as: relay 1 = alarm 1, high alarm at 0.25 m;
relay 2 = alarm 2, low alarm at 5.00 m.
To change the setpoints by reference method, set the material or target to the distance as
displayed. Press the 1/↑ or 2/↓ key. The display shows the current setpoint function and
value. Press the alarm key a second time so the device changes the setpoint to the value
currently being measured. After viewing or changing the setpoint, the device reverts to the
run mode.
Relay 1
1. Position the unit so that it reads 0.75 m.
2. Press 1/↑
3. Press 1/↑
4. Once installed, the unit will register a high alarm at 0.75 m from the sensor face. If Loss of
Echo
Pointek ULS200
Operating Instructions, 01/2019, A5E32268616-AB
Function display: high alarm
⇒
⇒
appears, complete steps 1 to 3 again.
Echoes are valid and within range.
Echoes are lost due to poor conditions or out of
range. This may be typical in applications where
there are deep vessels and the material level is
normally out of range. Refer to Troubleshooting
(Page 38).
Extended loss of echo period. Operation has
gone into fail-safe. Refer to Troubleshooting
(Page 38).
Current setpoint, 0.5 m
⇒
⇒
13