Siemens SKB60 Manuel - Sayfa 2

Anahtar Siemens SKB60 için çevrimiçi göz atın veya pdf Manuel indirin. Siemens SKB60 32 sayfaları. Auxiliary switch
Ayrıca Siemens SKB60 için: Montaj Talimatları (6 sayfalar), Montaj Talimatları (10 sayfalar), Montaj Talimatları (7 sayfalar), Montaj Talimatları (6 sayfalar), Montaj Talimatları (10 sayfalar), Montaj Talimatları (4 sayfalar)

Siemens SKB60 Manuel
Use
For the operation of Siemens 2-port and 3-port valves of the types VVF.., VVG.., VXF.. and
VXG.. with a 20 mm stroke as control and safety shut-off valves in heating, ventilation and
air conditioning plants.
Technical design
Principle of electro-hydraulic actuators
Opening the
valve
Closing the
valve
Manual
operation
mode
2
Siemens
Smart Infrastructure
Valve closed
The hydraulic pump [6] forces oil from the suction chamber [3] to the
pressure chamber [8], thereby moving the pressure cylinder [2] downwards.
The valve stem [11] retracts and the valve opens. Simultaneously, the return
spring [4] is compressed.
Activating the solenoid valve [5] allows the oil in the pressure chamber to
flow back into the suction chamber. The compressed return spring moves
the pressure cylinder upwards. The valve stem extends and the valve
closes.
For manual operation, swing out the crank so that the display window
becomes visible. By rotating the crank clockwise, the pressure cylinder is
moved downwards. The display window shows the engagement bar and/or
the scale dial with stroke indication.
In the manual operation mode, the positioning signals Y and Z can further
open the valve but cannot move to the 0 % stroke position of the valve. To
retain the manually set position, switch off the power supply or disconnect
the positioning signals Y and Z. The crank remains swung out and in the
display window the red indicator dial remains visible.
Note:
When setting the controller to manual operation for a longer
period of time, we recommend adjusting the actuator with the
manual adjuster to the desired position. This guarantees that
the actuator remains in this position for that period of time.
Attention: Do not forget to switch back to automatic operation
after the controller is set back to automatic control.
Valve opened
1
Manual adjuster
2
Pressure cylinder
3
Suction chamber
4
Return spring
5
Solenoid valve
6
Hydraulic pump
7
Piston
8
Pressure chamber
9
Position indicator (0 to 1)
10
Coupling
11
Valve stem
12
Plug
CM1N4564en
2023-10-17