Cisco 12006 series Değiştirme Talimatları Kılavuzu - Sayfa 30
Ağ Yönlendiricisi Cisco 12006 series için çevrimiçi göz atın veya pdf Değiştirme Talimatları Kılavuzu indirin. Cisco 12006 series 44 sayfaları. Chassis replacement instructions
Ayrıca Cisco 12006 series için: Ambalajdan Çıkarma Talimatları Kılavuzu (16 sayfalar), Veri Sayfası (9 sayfalar)
Reconnecting Power to a Router Equipped with the AC Power Distribution Unit
To reconnect source AC to the AC PDU, see
Attach an ESD-preventive wrist strap to your wrist and connect the leash to the chassis or to another
Step 1
grounded, bare metal surface. (See
Step 2
Beginning with the AC receptacle on the right side of the PDU, pull back the retention clip and plug the
AC power cord coupler for that receptacle into the AC receptacle.
Step 3
Release the retention clip over the power cord coupler to secure the power cord coupler in the AC
receptacle.
Step 4
Repeat Step
Reconnecting Power to a Router Equipped with the DC Power Distribution Unit
To reconnect source DC power to the DC PDU, see
Step 1
Attach an ESD-preventive wrist strap to your wrist and connect the leash to the chassis or to another
grounded, bare metal surface. (See
Step 2
Locate the power connector blocks on the PDU, and identify the negative, positive, and ground ports.
Before proceeding to the next step, verify that the DC circuit breaker servicing the DC power cable you
Caution
are installing is switched off. As an important extra check, measure the voltages across the cable leads.
All readings should be zero volts.
When installing the source DC power cable leads, always make the ground connection first.
Warning
Connect the source DC cable leads in this order: ground, positive, and negative.
Step 3
a.
b.
c.
Verify that the polarity of the source DC wiring from the source DC breaker to the PDU connector block
Step 4
is correct and that the terminal connections are tight.
Installing the Blower Module
After the chassis power has been reconnected to the PDU, install the blower module on the replacement
chassis.
To install the blower module, see
Cisco 12006 and Cisco 12406 Router Chassis Replacement Instructions
30
2
and Step
3
for the remaining AC receptacle and power cord.
Insert the exposed end of the wire into the corresponding terminal in the connector block.
Hold the wire in place and use a flat-blade screwdriver to tighten the clamping screw and secure the
wire.
Repeat Step
3a
and Step
3b
Figure 7
and follow these steps:
Figure
4.)
Figure 8
Figure
4.)
for the remaining power leads on both PDU connector blocks.
Figure 17
and follow these steps:
and
Figure 9
and follow these steps:
78-16109-01