C. Framing Enclosure for LP Gas Supply
System
If you build an enclosure for an LP gas cylinder, follow
these recommended specifications and local codes:
Ventilation
Enclosures must be ventilated by openings at the level
of the cylinder valve and at floor level. Effectiveness
must
be determined with the cylinder(s) in place.
• One side of the enclosure must be completely open
or,
• For an enclosure having four sides, a top and a bot-
tom:
- At least two ventilation openings at cylinder valve level
shall be provided in the side wall, equally sized, spaced
at 180 degrees (3.14 rad), and unobstructed. Each
opening must have a total free area of not less than 1/2
square inch per pound (3.2 sq.
capacity and not less than a total free area of 10 square
inches (64.5 sq. cm).
- Ventilation opening(s) must be provided at floor level
and shall have a total free area of not less than 1/2
square inch per pound (3.2 sq. cm/kg) of stored fuel
capacity and not less than a total free area of 10 square
inches (64.5 sq. cm). If ventilation openings at floor lev-
el are in a side wall, there must be a least two open-
ings. The bottom of the openings must be at floor level
and the upper edge can't be more than 5 in. (127 mm)
above the floor. The openings must be equally sized,
spaced at 180 degrees (3.14 rad) and unobstructed.
- Every opening must have minimum dimensions to
permit the entrance of a 1/8 inch (3.2 mm) diameter
rod.
cm/kg)
of stored fuel
Accessibility
• Cylinder valves must be readily accessible for hand
operation. A door on the enclosure to gain access to
the cylinder valves is acceptable, provided it is non-
locking and can be opened without the use of tools.
• The design of the enclosure must be such that:
- The LP gas supply cylinder(s) can be connected, dis-
connected and the connections inspected and tested
outside the cylinder enclosure.
- Those connections which could be disturbed when
installing the cylinder(s) in the enclosure can be leak
tested inside the enclosure.
- Be certain to mount or set the LP gas cylinder on a flat
stable surface and retain it to prevent it from tipping.
Minimum Clearances
• There must be a minimum clearance of 2 in. (50.8
mm) between the lower surface of the floor of the LP
gas supply cylinder enclosure and the ground.
7