2.3

Connection Specifications of Input Power

This section describes the connection specifications of Input power of the base cabinet of Cisco C880 Server.

2.3.1 Input Power Connection Specifications (Base Cabinet)

Following table shows the input power connection specifications of the main unit.
Destination
100 V
200 V
Remarks
-
Power cable supplied with the device and power cord supplied with the option part, are used for the
power cable which is connected to the device. However, the supplied power cable is not used for the
other products.
-
Power distribution box which is suitable to recipient power distribution format is used

2.3.2 Power Distribution Box and Distribution Panel

Following table shows the power supply cable specifications of power distribution box and distribution panel.
TABLE 2.2 Power Supply Cable Specifications of Power Distribution Box and Distribution Panel
Destination
200V for countries
other than Japan
200V for Brazil
Remarks
Power cable supplied with the device and power cord supplied with the option part, are not used for the
power cable which is connected to the device. However, the supplied power cable is not used for the other
products.
TABLE 2.1 Power Cable Specifications (Base Cabinet)
Plug format
Parallel 2-pole plug
with earthing-contact
"NEMA standard 5-
15P"
IEC60320-C20 type
Plug format
NEMAL6-30P
IEC60309-32A
Connection at wall-mount power distribution
Recipient power distribution
format
Connection at power distribution box
Recipient outlet format
Recipient power
distribution format
Recipient power
distribution format
17
Remarks
Power distribution "NEMA
standard 5-15R" for parallel
2-pole plug with earthing -
contact (125V 15A)
IEC60320-C19type
Remarks
NEMA L6-30R (30A-
220V)
IEC60309-32A (32A-
250V)