Battery test/Mute combination
(
)
+
Scroll
or
Setting entry
NO
Working status
1
Normal voltage
High/low voltage
protection, turn to
battery mode
2
Normal voltage
Battery Voltage abnormal
warning
3
Main AC Normal voltage
in bypass mode
Main AC high voltage
warning in bypass mode
Main AC low voltage
warning in bypass mode
4
Bypass mode
Press and hold the key for more than 1 second in Line mode or economic
(ECO) mode: UPS runs self-test function.
Press and hold the key for more than 1 second in battery mode: UPS runs
mute function.
Non-function setting mode:
Press and hold the key for more than half a second (less than 2 seconds):
Indicate the items of the LCD item section orderly.
Press and hold this key for more than 2 seconds: Circularly and orderly
display the items every 2 seconds, when press and hold the key for some
time again, it will turn to output status.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds):
Select the set option.
Non-function setting mode:
Press and hold the key for more than 2 seconds: Function setting
interface.
Function setting mode:
Press and hold the key for more than half a second (less than 2 seconds):
Affirm the set option.
Press and hold the key for more than 2 seconds, exit from this function
setting interface.
Table 3. Working status of indications
Indication
Nor
Bat
●
●
●
●
●
★
●
Battery disconnect warning
Warning
Bps
Fau
Line mode
Once every
★
four seconds
Battery mode
Once every
★
four seconds
Once per second
★
Bypass mode
Once every
★
●
two minutes
Once every
★
four seconds
Once every
★
four seconds
Once every
★
●
four seconds
None
Eliminate after starting the
UPS
Affirm if the battery switch
is closed
Remarks