Crouse-Hinds MTL F300 Kullanım Kılavuzu - Sayfa 7

Kontrolör Crouse-Hinds MTL F300 için çevrimiçi göz atın veya pdf Kullanım Kılavuzu indirin. Crouse-Hinds MTL F300 20 sayfaları.

Crouse-Hinds MTL F300 Kullanım Kılavuzu
the careful routing and securing of all cables.
d) Provide adequate security against unauthorized interference.
e) Conform to the permitted ambient temperature range of –45°C to +70°C.
4 .2 .2
In addition to the General Requirements above, if the Megablock is mounted in an
outdoor location, use a suitable enclosure with a minimum of IP54 ingress protection.
A higher level of ingress protection rating will be necessary if the working atmosphere
is, or can be, corrosive, or if the enclosure is subject to wet or dusty environments.
4 .3

DIN-rail mounting

The Megablocks are designed for mounting on 35mm x 7 .5mm T-section "top hat" DIN
rail to EN50022 and use built-in DIN rail clips to attach to the rail.
4 .3 .1
Megablocks are attached to the DIN rail using a "push-and-tilt" method - as illustrated
on the body label and in Figure 4.1 below.
Tilt the Megablock towards the trunk-connector side of the Megablock and then
engage the DIN-rail clips under the ledge of the DIN rail. Push the Megablock against
the edge of the rail then rotate the Megablock until it sits flat onto the DIN rail, then
release the pressure to allow the clips on the other side to engage.
Figure 4 .1: DIN Rail Installation and Removal
4 .4

Removal from DIN-rail

Refering to Figure 4.1, push the Megablock against the edge of the DIN rail, tilt the
other side of the Megablock up and away from the DIN rail, then release the side
pressure to disengage the DIN rail clips from the DIN rail ledge.
5

ELECTRICAL CONNECTIONS

The Trunk and Spur connectors are pluggable (with securing screws) and available
in the standard screw-terminal version or a spring-clamp version. Megablocks with
spring clamp connectors have a –PC suffix on the Megablock part number (-PC). See
Figures 5.1 and 5.2. The terminals can accept the following conductor sizes:
Type
Screw terminals
Spring clamp terminals (-PC)
A torque screwdriver set between 0.5 - 0.6Nm is recommended for tightening all
INM F300 rev 6
DRAFT - 09 July 2019
Outdoor mounting
Mounting procedure
1
Push
Conductor size
0.14 to 2.5mm
0.20 to 2.5mm
Remove
Install
2
2
NOTE
terminal screws.
2
3