Gaz Dedektörleri Crowcon TXgard-Plus için çevrimiçi göz atın veya pdf Talimatlar indirin. Crowcon TXgard-Plus 5 sayfaları. Flameproof toxic and oxygen gas detector

Instructions
TXgard-Plus
Flameproof
Toxic and Oxygen
Gas Detector
with Non-intrusive One-man Calibration
1. INTRODUCTION
1.1 Product overview
TXgard-Plus is a flameproof toxic and oxygen gas detector
suitable for use in zone 1 or 2 hazardous areas. It is designed to detect
the following gases when fitted with the appropriate electrochemical
sensor:
Gas
Hydrogen sulphide
0–25 ppm
Carbon monoxide
0–250 ppm
Ammonia
0–50 ppm
Oxygen
0–25% vv
Sulphur dioxide
0–10 ppm
A local display and magnetically operated switches allow non-
intrusive one-man calibration without a hot work permit. Powered by
24 V dc (nominally) TXgard-Plus provides a 4-20 mA signal (sink or
source) proportional to the gas concentration and can also be fitted
with optional alarm and fault relays.
1.2 Product description
TXgard-Plus comprises four parts; 96HD sensor housing, junction box, amplifier
and terminal board. Diagram 1 details TXgard-Plus. The overall assembly is
certified EEx d IIC T6 in Europe and Class 1 , Zones 1&2 AEx d IIC T6 in the USA.
The 96HD sensor housing is a modular stainless steel assembly that
dismantles to allow plug-in sensors to be replaced easily (see Diagram 4). The
assembly screws into an M20 entry on the junction box.
The junction box is manufactured from marine grade alloy and is supplied
with 2 x M20 (1/2" NPT for USA) cable entries for customer use. Alternative cable
entries are available from Crowcon.
The amplifier plugs into the terminal board, and is held in place by two
captive screws. The amplifier provides power to the sensor, local display and
controls, and a 4-20 mA signal proportional to the gas concentration for connection
to a control panel. To remove, turn screws anti-clockwise and use them to pull
amplifier out of the enclosure.
All electrical connections are made via the terminal board mounted in the
base of the junction box (see Diagram 2). Optional alarm relays (AL1 & AL2) and one
fault relay (FAULT) are mounted on the terminal board which may be used to drive
local warning devices or connect TXgard-Plus to a control panel.
Range
Type
Toxic
Toxic
Toxic
Oxygen
Toxic
1.3 Status Indication
TXgard-Plus includes a local display and status LED, visible through
the junction box window, see Diagram 1. The display shows the gas
concentration and current mode of operation ie. NORMAL, ZERO or CAL.
The LED shows the current alarm state of the detector. This is summarised in
Table 1.
Operational
LED
state
indication
Normal
Steady green
operation
Normal
Steady red
operation
(alarm 1)
Normal
Flashing red
operation
(alarm 2)
Over-range
Flashing red
Zero/calibration
Flashing green
mode
Detector
Steady amber
fault
*See section 2 for AL1 and AL2 standard settings
Table 1: LED status indicator summary.
UNITS
1
M20 (
/
" NPT)
2
CABLE ENTRY
STEADY ON
INDICATES
ZERO/ CAL
MODE
ACTIVATED
"UP"
EXTERNAL
EARTH POINT
Diagram 1: TXgard Plus general arrangement
1
Relay
Comment*
states*
AL1 - Off
Gas level < AL1
AL2 - Off
Current output = 4–20 mA
FAULT - On
AL1 - On
AL1 < gas level < AL2
AL2 - Off
Current output = 4–20 mA
FAULT - On
AL1 - On
Gas level > AL2
AL2 - On
Current output = 4–20 mA
FAULT - On
AL1 - On
Gas level > full scale
AL2 - On
Display backlight flashes
FAULT - On
Current output = 24 mA
Configuration
Latched until reset by 'MENU'
dependent
Current output = 2 mA
(see section 2) (4 mA option)
AL1 - Off
Current output = 0 mA
AL2 - Off
FAULT - Off
1
115 (4
/
")
2
TXgard-Plus
ppm
1
83 (3
/
")
4
All dimensions in mm unless otherwise stated
Relay version only
TAMPER PROOF
GRUB SCREW
(1.5mm ALLEN KEY)
LOCAL
DISPLAY
1
M20 (
/
" NPT)
2
CABLE ENTRY
FLASHING
INDICATES
4-20mA/RELAYS
INHIBITED
ALARM 1 & 2
ADJUSTMENT
POTS
STATUS
LED
"DOWN"
4 OFF
FIXING HOLES
1
O 6mm (
/
")
4
1
HEIGHT = 115 (4
/
")
2