Ariston 41-116-07 Kurulum Talimatları Kılavuzu - Sayfa 21
Kazan Ariston 41-116-07 için çevrimiçi göz atın veya pdf Kurulum Talimatları Kılavuzu indirin. Ariston 41-116-07 48 sayfaları. Microsystem
5.
GAS ADJUSTMENTS
CATEGORY II2H3+
Lower Wobbe Index (15°C;1013mbar)
Nominal Delivery Pressure
Minimum Delivery Pressure
21 RFFI
Main Burner: n. 12 jets (ø)
Consumption (15°C; 1013mbar)
Consumption (15°C; 1013mbar)
Gas Burner Pressure:
max - min
28 RFFI
Main Burner: n. 14 jets (ø)
Consumption (15°C; 1013mbar)
Consumption (15°C; 1013mbar)
Gas Burner Pressure:
max - min
[1 mbar = 10,197 mmc.a.]
5.1
C
HANGING THE
T
G
YPE OF
AS
Methane Gas
G20
MJ/m
3
h
45.67
mbar
20
mbar
17
mm
1.30
m
3
/h
2.4 - 1.05
Kg/h
----
mbar
8.5 - 1.7
1.30
m
3
/h
3.15 -1.26
Kg/h
----
mbar
11.0 - 1.6
The outlet pressure of the gas cock is obtained by completely loosening the
screw on the solenoid. The maximum pressure of the gas to the burner will
be equal to the nominal delivery pressure minus the head loss within the
gas valve.
The boiler can be converted to use either methane (natural) gas (G20)
or LPG (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner (see table in section 5);
2. Adjust the maximum and minimum thermal capacity values for the boiler
(see table in section 5);
3. Replace the gas rating plate;
4. Adjust the maximum thermal power setting;
5. Adjust the soft-light feature (open the cover of the regulation screw on the
gas valve (see F
IG
installation requirements).
21
Liquid Butane Gas
G30
80.58
29
20
0.77
----
1.78 - 0.78
27.5 - 6.2
0.77
----
1.78 - 0.78
27.7 - 4.6
. 5.1). Rotate clockwise from min. to max. as per
F
. 5.1
IG
T
5.1
ABLE
Liquid Propane Gas
G31
80.58
37
25
0.77
----
1.76 - 0.77
37.4 - 8.0
0.77
----
1.76 - 0.77
35.5 - 6.0