I. Addressable Smoke Detector Sensitivity
Software Enhancement
The FACP software has been enhanced to include a feature which allows the control panel to monitor and printout the sensitivity of
each addressable smoke detector in the system. This eliminates the need for a service person to physically connect a test device to
each smoke detector in the field.
Detector Data
An addressable smoke detector's ability to detect smoke can change over time as a result of component deterioration due to
environmental contaminants and dirt. Each addressable smoke detector's data (sensitivity) can be printed by entering Read Status
mode. Pressing the Enter key on the control panel keypad will display the following LCD screen:
Enter Read Status mode by pressing 2 while viewing the preceding screen. The following screen will be displayed:
Pressing 2 to access the Print function will cause the following screen to be displayed:
To print each addressable smoke detector's data (sensitivity), press 3 for DET DATA while viewing the Print screen. A printout
similar to the following will be generated to an optional printer connected to the FACP.
****************************DETECTOR DATA******************************
DEVICE TYPE
SMOKE DET P01
SMOKE DET P02
SMOKE DET I03
SMOKE DET I04
The Chamber Reading should be within the indicated ranges for the following smoke detectors:
• SD350(T), D350P(R) and SD300(T) Addressable Ionization Smoke Detectors: 405 - 2100
• CP350 and CP300 Addressable Photoelectric Smoke Detectors:
If the addressable smoke detector's Chamber Reading is not within this acceptable range, clean the detector and check the
Chamber Reading again. If the reading is still not within the acceptable range, immediately replace the detector.
Refer to the Fire Alarm Control Panel manual's Programming section for additional information on accessing Read Status mode
and interpreting the smoke detector addresses.
Note: If a printer is not available, it is possible to use the HyperTerminal feature, found in the Windows
folder which is resident on most personal computers, to store the Detector Data information. Any settings which are configured
in this feature must reflect the printer settings detailed in the FACP manual. Refer to the Windows
the HyperTerminal feature.
1 = PROGRAMMING
2=RD STATUS 3=RD BAT
DISPLAY POINT=*/#,AA
HISTORY=1
PRN PRGRAM/STATUS=1
HISTORY=2 DET DATA=3
CHAMBER READING
1420
1362
1452
1350
PRINT=2
03:52P Fri 01/19/01
03:52P Fri 01/19/01
03:52P Fri 01/19/01
03:52P Fri 01/19/01
750 - 2100
TIME/DATE
©
program Accessories
©
manual for information on