Control Panel
Model 08100
Rev 4.0
Detection – Linear Heat Detection(only)
The panel may be installed with fire detection or with no detection.
If Detection required
simply connect the LHD cable to the detection circuit. Linear Heat Detection (LHD) is a line-
type form of fixed temperature heat detection used in common commercial and industrial
environments. This linear cable can detect a fire anywhere along its entire length. LHD Cable
detection systems are easy to design, install, operate and maintain. Max 500m of LHD Cable
can be used.
LHD Cable works using a twisted pair, tri-metallic conductors sheathed in
advanced thermal polymers. In a fire the LHD insulation will breakdown and make contact,
signalling the control panel of an alarm. As the LHD is not monitored by the panel – NO End of
Line resistor is required.
The linear cable must be installed appropriately for the risk area.