isolated, any change in the detector status, will cause the panel sounder to operate for 1
second as an alert of the status change, but the panel will remain isolated. The isolate function
will also silence the siren/strobe and the internal sounder but will not cancel the alarm or fault
indication.
Reset Function
9.3
To reset the control panel, press and hold Mode Switch 1 until 2 beeps are heard. Following a
reset, the control panel will automatically isolate.
operation, press Mode Switch 1 and ensure the "Isolated" LED turns off. Note: The control
panel cannot be reset if the activation sequence has been initiated. When the "Discharging"
LED is no longer illuminated, the reset function will become available again.
Test Function
9.4
The control panel includes a test function, enabling the operator to ensure that the control
panel is functioning correctly. To operate the test function, press and hold Mode Switch 1 until
3 beeps are heard. The test function will illuminate all LEDS on the control panel and operate
the internal sounder and any external siren/strobes for 2 seconds, and then return the control
panel to normal operation. The test function does not activate the suppression system. Note:
If any LEDS or siren/strobes do not operate, contact your supplier.
Discharging the Fire System
9.5
To manually discharge the fire system, press and hold both Mode Switch 1 and Mode Switch 2
continuously for 5 seconds. This will immediately operate any installed siren/strobes and any
shutdown relays, to warn any occupants. Manually discharging the fire system should only
performed during commissioning/servicing when the system has been appropriately isolated, or
in case of fire.
Alarm Silence
9.6
To silence the internal sounder and any installed siren/strobes that have operated due to an
alarm condition, press and hold Mode Switch 1 until a 1 beep is heard and the "Isolated" LED is
illuminated. This will also override any installed shutdown relays and allow for operation of the
equipment. Note: Equipment should not be operated until it has been rendered safe by the
appropriate authority. The control panel will remain in an alarm/fault condition until serviced
and reset.
Fire Detection and Activation System
Model 08451
To restore the control panel to normal
Rev 3.1