20. Troubleshooting
E-00 AIM not
recognised
Detector
E-01
Communications
Error
Detector is
connected but
E-02
not 'Found'
E-03 Compensation
limit reached
Detector missed
E-04
too many
readings
Detector is not
E-05
aligned
Rapid
E-06
Obscuration Fault
Signal Too High
E-07
Fault
Compensation
E-08
Level Not Zero
during 'SET'
Signal Strength
Out of Range
E-09
when 'SET'
selected
• Refer to manufacturer for
technical assistance
• Check wiring between
System Controller and
Detector (Voltage to
Detector should be 11—
13V)
• Follow 'Find' process and
align if necessary
• Clean and realign system
• Check voltage to Controller.
• Check voltage to Detector is
>11V
• Follow alignment procedure
• Ensure clear line of sight
from Detector to Reflector
• Ensure clear line of sight
from Detector to Reflector
• Ensure there is no strong
light on Detector
• Re-align Detector using
Auto-Align
• Ensure Reflector uncovered
when 'SET' selected
• Ensure clear line of sight
from Detector to Reflector
for a radius of 0.5m
• Ensure correct distance has
been selected
• Ensure correct Reflectors
have been used
• Realign Detector
Reflector Not
Found during
E-10
Auto-Align
E-11 Auto-Align Failed
Cannot Zero
During 'S-00' in
'Set'
E-12
Signal did not
decrease when
'S-00' selected
No Signal During
'S-01' in 'Set'
E-13
Signal did not
increase when
'S-01' selected
'Centre' Stage of
Alignment Failed
Detector has
E-14
aligned on
something other
than the
Reflector
Power too low
E-21
fault
Detector not
E-24
compatible
Internal
E-26
controller fault
15
• Ensure clear line of sight
from Detector to Reflector for
a radius of 0.5m
• Ensure correct distance has
been selected
• Ensure correct Reflectors
have been used
• Realign Detector
• Ensure clear line of sight
from Detector to Reflector for
a radius of 0.5m
• Ensure correct distance has
been selected
• Ensure correct Reflectors
have been used
• Realign Detector
• Ensure Reflector was
completely covered with a
non-reflective material
• Re-align Detector using
Auto-Align
• Ensure Reflector was
uncovered when 'S-01' was
selected
• Ensure clear line of sight
from Detector to Reflector for
a radius of 0.5m
• Check power supply to
Controller
• Refer to manufacturer for
technical assistance
• Refer to manufacturer for