QUICK USER GUIDE FOR 1-8 ZONE FIRE PANELS
USER CODE
3545
LEVEL 2a
5344
LEVEL 2b
INDICATORS
FAULT /TEST
/DISABLE –
COMMON
FIRE - COMMON
ZONES 1-8
FAULT
ZONES 1-8 FIRE
SUPPLY
SUPPLY FAULT
DISABLED
ALARM FAULT/
DISABLED
ALARM
SILENCED
TEST
EARTH FAULT
SYSTEM FAULT
DELAY ENABLED
BUTTON
1
– RESET
2
– SILENCE
BUZZER
3
– SILENCE /
SOUND ALARMS
4,5 – WALK TEST
5
– LAMP TEST -
EXIT
1
– RESET
2
– SILENCE
BUZZER
3,4
– DISABLE /
ENABLE ZONE
5
– EXIT
COLOUR
Yellow
Red
Yellow
Red
Green
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
Yellow
16
Return the system to a normal condition after a fire or fault
has occurred. This should only be performed when the fire
or fault has been identified and alarms have been silenced.
Stops the sounding of the internal buzzer.
Turn off the fire alarm sounders whilst the system is being
cleared after a fire. Sound the fire alarms to evacuate the
building. Other devices will not be triggered
Tests detectors and callpoints on a zone. The sounders will
sound for 1 second then reset.
Zones tested are indicated on the panel
Lights all LEDs and beeps the internal buzzer for 2 seconds.
Then exits from Level 2a function
Return the system to a normal condition after a fire or fault
has occurred. This should only be performed when the fire
or fault has been identified and alarms have been silenced.
Stops the sounding of the internal buzzer.
Disable zones & alarms if a fault occurs – does not affect
the other zones. Select as follows:-
3 - Selects/deselects the zone/alarm
4 - Moves flashing light to the required zone.
Exit from Level 2b function.
INDICATION
On when a fault condition has occurred, or if no other fault
Led is on, this indicates 24v auxiliary fuse has tripped.
On when a FIRE condition has occurred.
Flashes if a detector is removed from its base, or an
open/short circuit zone wiring fault.
On when a zone is disabled and flashed when in walk test.
On during a FIRE condition in this zone.
Flashed when a device has been tested during walk test.
On while power is being supplied to the panel.
Flashes during a mains or battery supply failure.
Zones and / or alarm are disabled. The specific zone or
alarm fault led will also be lit.
Flashes with a fault on the sounder wiring.
Illuminated if alarm lines are disabled.
Sounders on the alarm circuits during a fire/evacuation
condition have been switched off.
Walk test function selected.
Will illuminate if a fault occurs with the earthing.
Illuminated if the panel has "crashed" and an attempt to
restart the system has been made. Flashed if an error in the
system software has been detected – Requires attention.
Alarms are delayed if switch is activated.
ACTION