DIP SWITCH B
1
costant flow
on
enabled
0
disabled
default
DIP SWITCH B
2
humidistat
on
disabled
0
AUTO
default
DIP SWITCH B
3
timer
on
disabled
AUTO
default
0

DisPosal anD rECYClinG

Information on disposal of units at the end of life.
This product complies with EU Directive 2002/96/EC.
The symbol of the crossed-out dustbin indicates that this product must be collected separately
from other waste at the end of its life. The user must, therefore, dispose of the product in question
at suitable electronic and electro-technical waste disposal collection centres, or else send the
product back to the retailer when purchasing a new, equivalent type device.
Separate collection of decommissioned equipment for recycling, treatment and environmentally
compatible disposal helps to prevent negative effects on the environment and on health and
promotes the recycling of the materials that make up the equipment.
Improper disposal of the product by the user may result in administrative sanctions as provided
by law.
Constant FloW oPEration
When the constant flow operation in enabled, the unit speeds up or slows
down depending on the variations of the resistances caused by long length
ducting or external windy conditions.
The constant flow operation can be enabled/ disabled by means of switch 1
of Dip Switch B.
HuMiDistat
The unit is equipped with a humidity sensor that operates in AUTO mode, i.e.
the humidistat, which records the humidity levels, triggers if there is a steep
variation of the humidity and if humidity level is over 65%. If the humidistat is
activated, the unit runs at the intermediate speed and continues to run for a
fixed time of 5 minutes after the umidity level stabilizes.
The humidistat can be enabled/ disabled by means of switch 2 of Dip
Switch B.
run-on tiMEr
The unit is equipped with a run-on timer. When the external switch is turned
off, the unit continues to run at the intermediate speed for the a period of time
defined as follows:
- if the external switch is activated for less than 3 minutes, the unit does not
run-on;
- if the external switch is activated for between 3 and 10 minutes, the unit
runs on for 5 minutes;
- if the external switch is activated for between 10 and 20 minutes, the unit
runs on for 10 minutes;
- if the external switch is activated for over 20 minutes, the unit runs on for
15 minutes.
When the time is expired, the unit returns to the minimum continuous speed.
The run-on Timer can be enabled/disabled by means of switch 3 of Dip
Switch B.