MPSC-2000 technical data and
specification guide
Protection: Trip settings shall be displayed on demand, and shall be user-
selectable at local or remote locations. Password access is required to
restrict changes by unauthorized personnel. Protective functions and
settings shall consist of the following parameters: [*refer to IB 6.1.2.8-1A
for values]
MPSC-2000 (current) Settings
Rating
0.5 or 1.0 X breaker rating
LT Pickup
0.5 - 1.0 X sensor rating (increments of 0.1)
LT Delay
Minimum, Intermediate, Maximum *
ST Pickup
2-12 X sensor rating (integral increments) or
DISABLED
ST Delay
Minimum, Intermediate, Maximum *
ST Curve
Definite, I
T
2
INST Pickup
3-12 X sensor rating (integral increments) or
DISABLED if INST not blocked
Ground Pickup
See ground sensor table *
Ground Delay
Minimum, Intermediate, Maximum *
Ground Curve
Definite, I
T
2
Test Curve
Long time, Short time, Instantaneous, Ground
Demand Interval
15, 30 and 60 minutes
I Unbalance
5-50% (increments of 1%)
I Unbalance Delay
0.1 - 25.0 sec (increments of 0.1%) or DISABLED
VIM (voltage) Settings
V Unbalance
5-50% (increments of 1%)
V Unbalance Delay
0.1 - 25.0 sec (increments of 0.1%) or DISABLED
UV Pickup
1 - 600 volts (increments of 1 volt)
UV Delay
0.1 - 25.0 sec (increments of 0.1%) or DISABLED
Demand Interval
15, 30 and 60 minutes
Metering: The following metering information shall be shown on
demand on an easily readable LCD display with a minimum of 2x16
characters. Data selection is available by local keypad access or remote
interrogation. Current and voltage measurements shall be within 1% of
the circuit breaker rating and power indications within 2% of breaker
rating. This information shall be available with applicable options to
remote control systems through the communications features of the
device.
[*displayed only if optional VIM is attached]
Load Values
Ia, Ib, Ic or In
*Van, Vbn, Vcn, Vab, Vbc, Vca
*KW30, KVar30, KVA30, KWHr30, KVarHr30
*Power Factor
*Frequency
Demand Values
Ia, Ib, Ic or In
*KW30, KVar30, KWHr30, KVarHr30
Records Information: The trip device shall provide access to trip records
on the LCD display as follows. This information shall be available to
remote control systems through the communications features of the
device.
MPSC-2000 (current) Trip Events
Fault ID: 1-16 (last event displayed at device; others are remote readable)
Event type:
[LT, ST, INST, GRND]
Phase A, B, C or Neutral current: [readout in amps]
Breaker Operations
Counter number:
[quantity]
Phase A, B or C KSI:
[readout in kA]
VIM (voltage) Trip Events
Event type:
[I Unbal, V Unbal, UV]
Vab, Vbc or Vca:
[readout in volts]
Each low voltage power circuit breaker shall be supplied with a
breaker-mounted microprocessor device with 3-phase and
neutral protection, metering and communications capabilities.
The device shall comply with the requirements of ANSI C37.17.
Standard trip functions shall include Long Time (LT), Short
Time (ST), Instantaneous (INST) and Ground (GRND) current
protection.
S
A
: The trip unit will be suitable for 3-phase
YSTEM
PPLICATION
systems, with or without a neutral connection, and voltages
between 208 and 600 VAC
RMS
be suitable for continuous currents up to 4200 amps, ground
currents up to 1200 amps, and short circuit currents up to
130kA.
P
: Tripping functions shall be self-powered, requiring no
OWER
auxiliary power source. Trip system memory shall be non-volatile
and shall not require battery back-up or other control power to
retain stored information. A battery or other power source must
be provided for metering, interrogation and to change settings
when the breaker is not energized. The battery must be a
common "off the shelf " device.
E
: The trip device shall operate in an ambient
NVIRONMENT
temperature range from -20
1) employ active and passive filtering techniques, 2) be
impervious to and not have false operation due to EMI or RFI
from any source as demonstrated by satisfactory testing in
accordance with ANSI standards C37.90.1 and C37.90.2,
respectively.
D
: The device shall include the ability to view protection
ISPLAY
settings, modify protection settings with password authorization,
view metering data and view operational history.
V
S
R
OLTAGE
OURCE
EQUIREMENT
system and for the trip device metering displays shall be derived
by direct connections to the three phases of the circuit breaker
being interrogated in order to retain the correct time
relationships for power calculations. Circuit breaker-mounted
potential transformers (PT's) shall condition the voltage signal
for use by the trip system voltage interfaces.
6
Specification Guide
at 50 or 60 Hz. The device must
o
o
C to +55
C.
The unit shall
: Voltage information for the