Armstrong FLO-RITE-TEMP 415DW Kurulum ve Ayarlama Talimatları - Sayfa 2

Su Isıtıcı Armstrong FLO-RITE-TEMP 415DW için çevrimiçi göz atın veya pdf Kurulum ve Ayarlama Talimatları indirin. Armstrong FLO-RITE-TEMP 415DW 20 sayfaları. Instantaneous water heater. instructions for single and double wall units
Ayrıca Armstrong FLO-RITE-TEMP 415DW için: Kurulum ve Ayarlama Talimatları (17 sayfalar)

Armstrong FLO-RITE-TEMP 415DW Kurulum ve Ayarlama Talimatları
INSTALLATION AND ADJUSTMENT INSTRUCTIONS
No water heater will work satisfactorily if improperly installed and operated. These instructions contain important
information for the installation and adjustment of the FLO-RITE-TEMP Water Heaters. Read these instructions carefully
before installing this unit. FAILURE TO ADHERE TO THESE INSTRUCTIONS COULD RESULT IN SERIOUS
BODILY INJURY OR PROPERTY DAMAGE.
STEAM PIPING INSTALLATION OF A SINGLE UNIT
Single and Double Wall
NOTE: FLO-RITE TEMP is provided with (1) one Armstrong Steam Trap and Thermostatic Air Vent
(shaded). All other items shown not included.
NOTE: units may be piped in parallel for larger capacity requirements. See Fig. 15-1 for an example of parallel unit
installation.
The unit includes the mixing valve mounted to the heat exchanger, channel iron and U-bolts mounted, thermostatic
air vent installed on the heat exchanger, a water pressure pop off valve integral to the unit control valve and a separate
Armstrong Inverted Bucket Steam Trap.
1.
Install the FLO-RITE-TEMP with adequate room to allow for tube bundle removal when cleaning is required. See
Table 12-1 for specific dimensions.
2.
If 2-15 psig of steam is available a pressure reducing valve is NOT required. If a pressure reducing valve is required,
an Armstrong Inverted Bucket Steam Trap is recommended to drain condensate at the inlet of the pressure reducing
valve.
3.
An Armstrong Y-strainer should be installed before the pressure reducing valve to reduce the chance of dirt
fouling.
FLO-RITE-TEMP
INSTANTANEOUS WATER HEATER
NOTICE
Steam In
Armstrong Pressure
Reducing Valve (if req'd)
Armstrong
TVS Trap
Armstrong Thermostatic
Vacuum
Breaker
STEAM SIDE INSTALLATION
(Refer to Fig. 2-1)
Safety Relief
Valve
Gate
Valve
GP-2000
Pressure
Gauge
Air Vent
2-15 psig Steam
in the Shell
Armstrong
I.B. Trap
Fig. 2-1
2