Acorn Safety S0402 Kurulum, Çalıştırma ve Bakım Talimatları - Sayfa 3
Çim ve Bahçe Ekipmanları Acorn Safety S0402 için çevrimiçi göz atın veya pdf Kurulum, Çalıştırma ve Bakım Talimatları indirin. Acorn Safety S0402 5 sayfaları. Drench hoses
Installation & Operation Manual
INSTALLATION INSTRUCTION
Supplies required: (not provided by Acorn)
1.Wall fasteners, washers, anchors and screws.
2.Pipe sealant or Teflon tape for sealing water
connections.
IMPORTANT: FLUSH WATER SUPPLY LINES PRIOR
TO CONNECTION TO SAFETY EQUIPMENT.
Notes:
—
Use hand tools and wrenches in a manner which will
prevent marring finished surfaces. Strap wrenches or
tools with plastic jaw linings are highly recommended.
—
Refer to Rough-in for location of supply and drain
lines.
—
Fragments of Teflon tape or pipe sealant residue can
interfere with the proper operation of this unit. Ensure
pipe sealant methods do not cause contamination in
the system.
STEP ONE:MOUNTING
1. Determine desired mounting location and mark wall
using hanger mounting holes.
2. Install appropriate anchors to receive mounting
screws or bolts (supplied by others).
3. Re-position hanger over anchors and install mounting
screws to fasten hanger securely to wall.
4. Hang drench hose on hanger.
STEP TWO:SUPPLY LINE
1. Install water line (supplied by others) in close
proximity to drench hose location.
2. Connect 3/8" NPT reinforced hose (supplied with
drench hose) to plumbed water supply.
3. Open water supply.
4. Test for leaks, proper operation and flow.
STEP THREE:SINAGE & INSPECTION
1. Position sign with clear visibility, in close proximity to
safety equipment and mark mounting hole locations.
2. Select appropriate 1/4" anchors, screws and washers
(Supplied by others) to install signage.
3. Attach inspection tag supplied, with plastic zip tie.
Acorn Safety
a division of Acorn Engineering
Manual #7109-500-001
MOUNTING SCREW
(PROVIDED BY
INSTALLER)
BRACKETS PROVIDED
FOR WALL MOUNTED
MOUNTING SCREW
(PROVIDED BY
INSTALLER)
Company
™
Page 3 of 5
MODELS
3/ 8" FITTING
CONNECT TO
WATER LINE
(SUPPLIED BY
INSTALLER)
Revised: 03/22/13