3. OVERVIEW
This manual provides general settings and is not a comprehensive guide to the
programming and configuration of a specific installation. An installation may
have unique conditions or use cases that require modification or adaptations of
values. Installers must be capable of reviewing and adapting to the specifics of an
installation and its specific use case and optimizing settings where needed.
• Review and confirm equipment compatibility and correct sizing.
• Configure the LYNK II Communication Gateway's CAN out pins to match the CAN
in pins of the power conversion equipment.
• Mount the LYNK II Gateway, connect the Discover battery communication
network to either the LYNK Port or AEbus Port, and then connect the CAN Out
Port to the power conversion equipment's communication network.
• Terminate all networks correctly.
• Set the LYNK II Gateway using LYNK ACCESS software to the correct protocol
to enable closed-loop communication between the Discover batteries and the
power conversion equipment.
• Set up user preferences and enable the use case using the power conversion
control system.
3.1 System Overview
The LYNK II Communication Gateway unlocks the full potential of a Discover
Lithium battery by enabling the internal Battery Management System (BMS)
to provide real-time data in a closed-loop configuration to other devices. This
configuration allows hybrid inverter-chargers and solar charge controller systems
to optimize control over the charging process in solar applications. LYNK II also
enables the remote monitoring of Discover Lithium battery SOC and data logging
of multiple sites using the data monitoring services offered by off-grid inverter
systems.
Discover Lithium batteries must be set up to work with SMA Sunny Island Inverter-
Chargers in a closed-loop configuration. In a closed-loop configuration, the BMS of
the Discover Lithium battery sends battery status over a network data connection
with the SMA Sunny Island Inverter-Charger. The SMA Sunny Island Inverter-
Charger uses the Discover Lithium battery BMS data to finetune the output of the
charger and deliver other functional controls based on battery voltage, temperature,
and percent State-of-Charge.
If communication is interrupted between the BMS and SMA Sunny Island Inverter-
Charger, after about 1 minute the power conversion device throws a fault (F952
MalfunctionExtBMSTimeout). Once communication is re-established, power
conversion device operations resume.
• SMA Sunny Island Inverter-Charger cannot be operated in an open-loop
configuration with Lithium batteries based on voltage-only charge settings.
NOTICE