Distech Controls LonWorks LonMark RCL-ITR Donanım Kurulum Kılavuzu

Kayıt Ekipmanları Distech Controls LonWorks LonMark RCL-ITR için çevrimiçi göz atın veya pdf Donanım Kurulum Kılavuzu indirin. Distech Controls LonWorks LonMark RCL-ITR 6 sayfaları. Certified room manager with interface and 4-channel rj9 inputs expander

LonMark
1.
Product Description
This document describes the hardware installation procedures for the
RCL-ITR LonWorks Interface.
The Distech Controls RCL-ITR Room Manager and Network Interface
are designed to provide direct connectivity between Distech Controls™'
RJ9 accessories and the LON network. Moreover, the RCL-ITR
embeds four room controller LonMark objects, increasing lighting
and sunblind management capability to suit the most demanding
configuration requirements.
The RCL-ITR uses the LonTalk TP/FT-10 communication protocol and
is LonMark certified.
Figure 1-1:
RCL-ITR Enclosure
2.
General Installation Requirements
For proper installation and subsequent operation of the module, pay
special attention to the following recommendations:
It is recommended that the module(s) be kept at room temperature
for at least 24 hours before installation to allow any condensation
that may have accumulated due to low temperature during
shipping/storage to evaporate.
Upon unpacking the product, inspect the contents of the carton for
shipping damages. Do not install damaged modules.
Avoid areas where corroding, deteriorating or explosive vapors,
fumes or gases may be present.
Allow for proper clearance around the module's enclosure, wiring
terminals and service pin to provide easy access for hardware
configuration and maintenance, and to ventilate heat generated
by the module. Remember to record the 12-character Neuron
located on either end of the module (shown on a sticker below the
barcode) for later commissioning.
Orient the module with the power supply terminal block connectors
towards the top to permit proper heat dissipation
www.distech-controls.com
Certified Room Manager with LonWorks
®
ID
®
Hardware Installation Guide
Interface and 4-Channel RJ9 Inputs Expander
®
The module's datasheet specifies the power consumption, the
operating temperature range, and other environmental conditions
the module is designed to operate under.
Do not drop the module or subject it to physical shock.
If the module is used and/or installed in a manner not specified by
Distech Controls, the functionality and the protection provided by
the module may be impaired.
Any type of modification to any Distech Controls product
will void the product's warranty.
Take special care to connector positioning when wiring.
Before installing a Wireless Receiver, verify that local
communication regulations allow the installation of
wireless devices that operate at a frequency of 868 MHz.
Refer to the Open-to-Wireless
more information.
Take reasonable precautions to prevent electrostatic
discharges to the module when installing, servicing or
operating the module. Discharge accumulated static
electricity by touching one's hand to a securely grounded
object before working with the module.
3.
Module Markings (Symbols)
Certain markings (symbols) can be found on the side of the module
and are defined as:
CE marking: conforms with the essential requirements of
the applicable EC directives.
Double Insulation Symbol: These modules are built with
double insulation.
Products must be disposed of at the end of their useful life
according to local regulations.
Read the notice.
For indoor use.
4.
General Wiring Recommendations
Turn off power before any kind of servicing
All wiring must comply with electrical wiring diagrams as well as
national and local electrical codes.
To connect the wiring to a module, use the terminal connectors.
Use a small flat screwdriver to tighten the terminal connector
screws once the wires have been inserted (coupling torque: 0.5
Nm).
RCL-ITR