dIXEL XC450D Kullanım Talimatları - Sayfa 3

Kontrolör dIXEL XC450D için çevrimiçi göz atın veya pdf Kullanım Talimatları indirin. dIXEL XC450D 3 sayfaları. Safety step controller

dIXEL XC450D Kullanım Talimatları
dIXEL
did
LL liquid alarm delay: 0 ÷ 255 min. Delay between the detection of the LL
liquid alarm condition and its signalling.
iP4
Alarm stop polarity from pressure switch: oP: the digital input is activated by
opening the contact; CL: the digital input is activated by closing the contact.
iP5
By-pass input polarity: oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
ALIP
Alarm input for compressors and fans polarity
oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
COMPRESSORS REGULATION
Pbd
Proportional band or neutral zone width (0.10÷10.0 bar). The band (or zone)
is symmetrical compared to the target set point, with extremes: SET-Pbd/2 and
SET+Pbd/2.
Onon
Minimum time between 2 following switching ON of the same compressor
(0÷255min).
oFon
Minimum time between the switching off of a compressor and the
following switching on (0÷255min)
don
Time delay between the insertion of two different compressors (0÷99.5
min; ris. 10s).
doF
Time delay between switching off of two different compressors (0÷99.5
min; ris. 10s).
odo
Count time with by-pass input ON (0÷255min)
LSE
Minimum set point for compressors.
HSE
Maximum set point for compressors.
ALARMS – COMPRESSOR SECTION
PAo:
Alarm probe exclusion at power on. it is the period starting from instrument
switch on, before an alarm probe is signalled. (0÷255 min). During this time if the
pressure is out of range all the compressor are switched on.
LAL:
Low pressure (temperature) alarm: The measurement unit depends on dEU
parameter. It's always subtracted to the set point. When the value SET-LAL is
reached the A03C alarm is enabled, (possibly after the tAo delay time).
HAL:
High pressure (temperature) alarm: The measurement unit depends on dEU
parameter. It's always added to the set point. When the value SET+HAL is
reached the A04C alarm is enabled, (possibly after the tAo delay time).
tAo:
Low and High pressure (temperature) alarms delay: (0÷255 min) time
interval between the detection of a pressure (temperature) alarm condition and
alarm signalling.
SPr:
Number of steps engaged with faulty probe. (0÷#compr).
OTHER
tbA
Alarm relay silencing: by pushing one of the keypad buttons. no= alarm relay
stays on; yES= alarm relay is switched off by pushing any keys.
OAP
Alarm relay output polarity: cL=closed when activated; oP= opened when
activated
oFF
Switching ON/OFF enabling from keyboard: (no = disabled; yES= enabled)
It permits the switching ON/OFF of the instrument by pressing the SET key for
more than 4s.
Ad1:
Compressors address (1 –247) It is used in monitoring system.
Ad2:
Fans address (1 –247) It is used in monitoring system.
Ptb
Parameter table code: readable only.
rEL
Software release for internal use.
Pr2
Access to the protected parameter list (read only).
TYPE OF REGULATION
- OFF: the instrument doesn't make the regulation; it detects the LL liquid alarm and the
P1 broken transducer.
- REGULATION ON: when the digital input is activated or set manually by pushing the
DOWN key for 3s. Compressors depends on th SetC and Pbd parameters.
- RESET REGULATION ON: turning off and on the controller, or with DOWN key during
3".
Functioning mode:
rtY=db neutral zone: If the pressure (temperature) is inside this zone the controller
maintains the same number of loads switched on and off, without changing anything.
When the pressure (temperature) go out from the zone, regulation starts.
rtY=Pb proportional band: The regulation band (Pbd) is divided into as many parts
as there are stages. The numbers of stages switched ON is proportional to the value
of the input signal: when this distances itself from the target set point and enters the
various bands, the compressors are switched ON, to be then turned OFF when the
signal brings near the set point. In this way if the pressure is greater than regulation
band, all the compressors are on, if the pressure (temperature) is lower than the
regulation band all the compressors are off.
SAFETY TIMES
A load is turned ON only if the safety times onon, oFon, donF are over.
Regulation stops when the pressure (temperature) come back into the neutral zone.
CONFIGURATION AND ALARM DIAGNOSTICS
DIGITAL INPUTS FOR COMPRESSOR SAFETY
ALIP: It establishes if the input is activated by closing (ALIP=cL) or by opening (ALIP=oP)
the id1, id2, id3 contacts.
Actions
Every time one input is activated the corresponding output is turned off.
P1 probe failure alarm
It is generated by failure in the transducer.
SPr: number of steps engaged with faulty probe.
1592001620 XC450D GB R1.0 10.07.2009
Operating instructions
It is an alarm signal with the activation of: relay, buzzer and P1 and P2 code display.
Recovery
Automatic as soon as probe restarts working.
HA, LA: LA2 High and low pressure (temperature) alarms
This alarm signals that the pressure (temperature) is out of limits established by
parameters LAL – SetC+ HAL.
The tAo and AFd parameters set the delay between alarm condition and alarm signalling.
Action
The alarm is signalled with standard action. The outputs are unchanged.
ALARM MUTING
Press any buttons to silence the buzzer during an alarm condition.
Hold pressed for more than 3 seconds switch off the alarm relay during an alarm condition
PARAMETERS – DEFAULT VALUES
Name
SEtc
oA4
oA5
oA6
rtY
StY
PA04
PA20
cAL
i1C
did
iP4
iP5
ALiP
Pbd
onon
oFon
don
doF
odo
LSE
HSE
PAo
LAL
HAL
tAo
SPr
tbA
OAP
oFF
Ad1
rEL
Ptb
Pr2
XC450D
bar
Level
Description
3.0 --
Set Point for pressure
Cpr Pr2
Output 4 configuration
Cpr Pr2
Output 5 configuration
Cpr Pr2
Output 6 configuration
db Pr2
Type of regulation
yES Pr2
Compressor rotation
0,5 Pr2
Adjustment of read out for the Probe at 4mA
8,0 Pr2
Adjustment of read out for the Probe at 20mA PA04 ÷ 51.0 bar
0 Pr2
Probe 1 calibration
DIGITAL INPUTS
CL Pr2
Liquid alarm polarity
60 Pr2
Liquid alarm signalling delay
CL Pr2
Alarm stop polarity from pressure switch
CL Pr2
By-pass input polarity
CL Pr2
Alarm input for compressors and fans polarity
REGULATION
0.6 Pr2
Proportional band of compressors
Minimum time between 2 following switching
5 Pr2
ON
Minimum time between the switching off and
2 Pr2
on
Time delay between the insertion of two
0,3 Pr2
different compressors
Time delay between switching off of two
0,1 Pr2
different compressors
10 Pr2
Regulation delay on start-up
0,5 Pr2
Minimum set point for compressors
4,0 Pr2
Maximum set point for compressors
PRESSURE ALARMS
30 Pr2
Alarm probe exclusion at power on
Low pressure (temperature) alarm –
10 Pr1
compressor section
High pressure (temperature) alarm–
10 Pr1
compressor section
Low and High pressure (temperature) alarms
10 Pr1
delay– compressor section
2 Pr2
Number of steps engaged with faulty probe
no Pr2
Alarm relay silencing
cL Pr2
Alarm relay output polarity
OTHER
Yes Pr2
Switching ON/OFF enabling from keyboard
1 Pr2
Serial address
- Pr2
Release micro
- Pr2
Parameter table code
Pr1
Password protected menu
1592001620
Range
LSE ÷ HSE
cPr / FAn / StP / ALr / Lin /
nu/Liq/MAn
cPr / FAn / StP / ALr / Lin /
nu/Liq/MAn
cPr / FAn / StP / ALr / Lin /
nu/Liq/MAn
db, pb
no / YES
0.0 bar ÷ PA20
-12.0 ÷ 12.0
oP / cL
0 ÷ 255 min.
oP / cL
oP / cL
oP / cL
> 0 ÷ 10.0 bar
0 ÷ 255 min.
0 ÷ 255 min.
0 ÷ 99.5 min.( res. 10 ")
0 ÷ 99.5 min. (res.10". )
0 ÷ 255 minuti
PA04 ÷ HSE
LSE ÷ PA20
0 ÷ 255 min.
> 0 ÷ 30.0 bar
> 0 ÷ 30.0
0 ÷ 255 min.
0 ÷ oA6
no / YES
oP ÷ cL
no / YES
1 ÷ 247
readable only
readable only
readable only
3/3