Electrical Supply

The operating voltage of the RMS-D II is +12 Volt (article number 08-101) or +24 Volt article number 08-
102) and is provided by the connecting plug.
The operating voltage of the RMS-V II is +12 Volt (article number
08-202) and is provided by the connecting plug.

Installation

Mounting Instructions

The following instructions are to be followed carefully in order to guarantee a
Attention:
safe and smooth operation. Not following these instructions can lead to false
alarms or additional error signals.
 The basic installation can be found in the VDS guidelines 2095 and other recognized technical rules
and norms and guidelines of specific countries are also to be regarded.
 Avoid mounting the smoke detector near sources of steam, dust, exhaust and other smoke particles
from the aerosol.
 The smoke detector must be mounted at least 1 m from the wall and in the correct alignment with the
window (see Fig. 1).
 A semi-circular area with a radius of 100 cm below the smoke detector must be free of permanent
objects and open doors and windows may not enter this area.
Fig.1: Aligning the Mounting
 Note: People, large animals, insects, plants and other objects that enter this area can cause an error
signal to go off.
Installationshandbuch: RMS-D II und RMS-V II Relais