Arthur Grillo DPC200-EP4000 Manuel - Sayfa 6
Kontrolör Arthur Grillo DPC200-EP4000 için çevrimiçi göz atın veya pdf Manuel indirin. Arthur Grillo DPC200-EP4000 7 sayfaları. Differential pressure controller
Adjustment:
controlling mode
∆P = 150 Pa
(1)
Press button T1
about 2 seconds
to start menu
menu
Press
button T2
Press
button T1
unit
metric
Press
Press
button T2
button T2
operating mode
measuring mode
Press
button T2
Press
button T1
parameter
parameter
diff. pressure
volume flow
Press
button T2
fan k-factor
unit
imperial
Press button T1
Press
button T2
Button T1: reset
Button T2: set
k = 70
Button T1: confirm
Display flashes once
back and confirm
menu
operating mode
controlling mode
Press
button T2
Press
button T1
parameter
parameter
diff. pressure
volume flow
Press
button T2
fan k-factor
Button T1: reset
setpoint 1
Button T2: set
50 Pa
Button T1: confirm
Display flashes once
Press
button T2
Button T1: reset
setpoint 2
Button T2: set
250 Pa
Button T1: confirm
Display flashes once
Press
button T2
Button T1: reset
output voltage
Button T2: set
U= 10,0 V
Button T1: confirm
Display flashes once
Press
button T2
Button T1: reset
P - parameter
Button T2: set
50
Button T1: confirm
Display flashes once
Press
button T2
Button T1: reset
I - parameter
Button T2: set
3,15
Button T1: confirm
Display flashes once
Press
button T2
controlling mode
normal
Press button T1
To leave menu
controlling mode
∆P = 150 Pa
Press button T2
to remain menu
5
Press
button T2
Button T1: reset
Button T2: set
k = 70
Button T1: confirm
Display flashes once
Press
button T2
Press
button T1
controlling mode
invers
Press
button T2
(1)