4. Operation

Configuring Battery Settings
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime configure the UPS for the correct number of
EBPs refer to Figure 3 for the appropriate setting of battery numbers and type. Use the
up and down buttons to select the number of battery strings according to your UPS
configuration:
Figure 3 – Battery number configuration
All UPS and EBP Cabinets
UPS only (internal batteries)
USV + 1 Extended Battery Pack
USV + 2 Extended Battery Packs
USV + 3 Extended Battery Packs
USV + 4 Extended Battery Packs
NOTE:
The UPS contains one battery string; each EBP contains two battery strings.
Page 8
Number of Battery Strings
1 (default)
3
5
7
9