1. General Information (Use this in conjunction with respective Installation Guide):
Altronix AL602ULADA, AL802ULADA and AL1002ULADA are very versatile devices. They can be used with or
without specific synchronization modules provided by some manufacturers. Multiple units can be synchronized by using
either the built-in sync mode or a external synchronization module. Please note, that only notification appliances with
synchronization capabilities can be synchronized. Contact signal manufacturer for more detailed information.
Units can operate with either one (1) or two (2) outputs from the FACP. Two (2) outputs from the NAC power
extender can be paralleled to achieve up to 4 amp, for circuits requiring additional power.
Note: Each output can be split into two (2) wire runs to achieve up to eight (8).
2. Paralleling Two (2) Outputs:
To parallel two (2) outputs for maximum NAC
capability of 4 amp, bridge (pos+) to (pos+) and (neg-) to (neg-)
(ex. +OUT3 to +OUT4 and OUT3 - to OUT4 -, Fig. 2). Both of
the corresponding output switches must be set the same way.
Install two (2) 2.2K ohm EOL resistors in parallel across the last
notification appliance.
Please note: Paralleled output circuit configuration is not power
limited and paralleling is not allowable for Class A configuration.
3. Class A and Class B Hookups:
Units can be used with the outputs configured for:
• Two (2) Class A (Fig. 3A).
• Up to Four (4) Class B (Fig. 3C).
Fig. 3A
SW2
SW1
+ OUT1 --
+ OUT2 --
+ OUT3 --
2 Class A
Hookups
NAC Loop 1 starts on Output 1 and
terminates on Output 3. Switch
SW1, when closed, provides proper
termination for this loop. NAC
Loop 2 starts on Output 2 and
terminates on Output 4, SW2 must
be closed for proper termination.
Please make sure that all the dip
switches for corresponding outputs
are set the same way.
• Two (2) Class B and one (1) Class A NAC circuits (Fig. 3B).
Fig. 3B
SW2
SW1
+ OUT4 --
+ OUT1 --
+ OUT2 --
IN1+ IN1--
IN2+
IN2--
C "DRY1" NC
RET1+ RET1--
RET2+
RET2--
C "DRY2" NC
From
Return
FACP
to FACP
NAC1
From FACP
NAC2
Return
to FACP
One (1) Class A, two (2) Class B Hookups
For combination of two (2)
Class B and one (1) Class A
circuit, only one (1) switch
(SW1 or SW2) must be closed,
terminating Class A circuit only.
Fig. 2
Fig. 3C
+ OUT3 --
+ OUT4 --
IN1+ IN1--
UPPER TERMINALS
RET1+
LOWER TERMINALS
2.2K
2.2K
EOL
EOL
Eight (8) wire runs
Connect two (2) wire runs to one (1) output
with a 4.7K EOL, (Altronix Model #
AL-EOL47) used to terminate each wire
runs.
Note: Both wire runs will be supervised.
A trouble condition on either wire run is
reported on the common signaling circuit.
However a short circuit on one wire run will
affect the other wire run on the same
signaling circuit. Keep wires on different
sides of the screw. DO NOT USE one (1)
continuous circuit around the terminal. This
is available to facilitate more wire runs from
the unit.
- 2 -
SW2
SW1
+ OUT1 --
+ OUT2 --
+ OUT3 --
2.2K
2.2K
EOL
EOL
Class B
single outputs
SW2
SW1
+ OUT1 --
+ OUT2 --
-- C "DRY1" NC
UPPER TERMINALS
--
-- C "DRY2" NC
LOWER TERMINALS
4.7K
4.7K
4.7K
4.7K
EOL
EOL
EOL
EOL
+ OUT4 --
2.2K
2.2K
EOL
EOL
Class B
paralleled outputs
+ OUT3 --
+ OUT4 --
IN1+ IN1-- I
RET1+ RET1-- R
4.7K
4.7K
4.7K
4.7K
EOL
EOL
EOL
EOL