Doc. Code: CE113100

Digital Inputs

Number of inputs
Input voltage
Input current
Input type
Input impedance
Insulation
Terminal block configuration
Response time
Status indication
Note
Response time: the maximum response time for general purpose digital inputs will be the response time plus the maximum
cycle time.
Altus S. A.
DU350, DU351
20 digital inputs divided into 3 insulation groups:
I00 to I08 – 9 inputs – Group 0
I10 to I18 – 9 inputs – Group 1
I20 to I21 – 2 inputs – Group 2
14 to 30 Vdc (common reference) for state 1
0 to 5 Vdc (common reference) for state 0
5 mA (24 Vdc common reference) – general purpose inputs
15 mA (24 Vdc common reference) – fast inputs
Sink, type 1
4.3 k – general purpose inputs
1.5 k – fast inputs
2000 Vac for one minute between each input group
2000 Vac for one minute between input group and logic circuit
The digital inputs are divided in 3 connectors (insulation groups)
insulated among themselves and insulated from the logic circuit.
Each connector is composed of a terminal block for each input and a
terminal block to the reference voltage.
I00 to I08 – input 0 to 8 of the insulation group 0
I10 to I18 – input 0 to 8 of the insulation group 1
I20 to I21 – input 0 to 1 of the insulation group 2
C0 – common of the insulation group 0
C1 – common of the insulation group 1
C2 – common of the insulation group 2
Inputs I00 to I02 and I10 to I12, are fast inputs. Inputs I00 to I02,
belong to Block 0 fast inputs; inputs I10 to I02 belong to the Block 1
fast inputs. Fast inputs can be used as general purpose inputs.
0,5 ms – general purpose inputs
10 s – fast inputs
Can be accessed via HMI at product standard screens
DU350, DU351
Revision: G